Installation Clearances; Tools And Instruments - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)

3.1.1.3 Installation Clearances

Reserve the following clearances around the cabinet to facilitate operations and
ventilation:
Figure 3-2 Reserved clearances (unit: mm)

3.1.2 Tools and Instruments

Insulate installation tools to prevent electric shocks.
Prepare the following tools and meters indicated in
Issue 15 (2022-01-30)
shorten the battery lifespan and operating temperatures lower than 20°C
reduce the battery backup time.
Reserve at least 800 mm from the front and rear of the cabinet.
Reserve at least 500 mm from the top of the cabinet.
If a top air-flow cabinet is deployed, the UPS can be installed against a wall
and no space needs to be reserved at the rear. If no top air-flow cabinet is
deployed, at least 500 mm space should be reserved at the rear for
ventilation. If the UPS will be operated from the rear, at least 800 mm space
should be reserved for operations.
CA UTION
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Table 3-1
for installation.
54