Output Electrical Specifications - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
Item
One-button cold start
Charger output power
Charger current limit
Battery string sharing
Charging voltage (lead-acid
battery)

7.8 Output Electrical Specifications

Item
Output system
Voltage
Frequency
Total harmonic distortion of
output voltage (THDv)
Output PF
Transfer time
Output voltage unbalance
Issue 15 (2022-01-30)
Specifications
In the case of a mains failure, batteries can start
the UPS to power loads.
Under rated conditions, the maximum charge
power of a module is 5 kW.
Maximum 10 A for a module
Battery string sharing is supported in a parallel
system. No battery string is shared by default.
● Equalized charge voltage: 2.3–2.4 V/cell,
● Equalized charge voltage: 2.3–2.4 V/cell,
● Float charge voltage: 2.23–2.3 V/cell, default:
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC±1% (line voltage)
● In normal mode, the mains frequency is
● In battery mode, the frequency is 50 Hz or 60
● ≤ 1% (100% linear load)
● ≤ 4% (100% non-linear load)
1
● 0 ms (uninterruptible transfer)
● ≤ 20 ms (interruptible transfer)
Voltage unbalance: ±3%; phase unbalance:
120±2°
Copyright © Huawei Technologies Co., Ltd.
default: 2.35 V/cell (30–42 batteries)
default: 2.35 V/cell (44 batteries)
2.25 V/cell (30–44 batteries)
synchronized with the bypass input frequency.
Hz (tolerance ± 0.05%).
7 Technical Specifications
189