Test Data Download - Huawei UPS5000-E User Manual

Hide thumbs Also See for UPS5000-E:
Table of Contents

Advertisement

UPS5000-E-(50 kVA–300 kVA)
User Manual (50 kVA Power Modules)
----End

4.6.3 Test Data Download

Issue 15 (2022-01-30)
NO TE
The capacity test automatically stops in any of the following cases:
● The minimum cell voltage reaches 2.65 V.
● The load fluctuation exceeds 10%.
● A fault alarm is generated.
The test is complete when the minimum cell voltage reaches 2.65 V. Data about the most
amount of energy discharged is stored once a month for 36 months.
Web
a.
On the WebUI, choose Query > Battery Test Records, choose logs that
need to be queried from the Log drop-down list box, and click Query.
Figure 4-14 Battery Test Records
b.
Select the queried logs and click Export.
Old Web
a.
On the WebUI, choose Query > Logs, choose logs that need to be
exported from the Log drop-down list box, and click Query.
Figure 4-15 Logs
b.
Choose logs that have been queried from the Log drop-down list box,
and click Export.
Copyright © Huawei Technologies Co., Ltd.
4 Operations
166