11.12 Group PIPE DATA

PIPE MATERIAL
Use this function to display the pipe material. This is specified by the option selected in the
function PIPE STANDARD. If you edit the predetermined value, the pipe standard will be
reset to the option OTHER and the function NOMINAL DIAMETER does not appear.
The pipe material must be selected if the option OTHER was selected in the function PIPE
STANDARD and thus a pipe standard is not defined.
Options:
CARBON STEEL
DUCTILE IRON
STAINLESS STEEL
ALLOY C
PVC
GRP
ASBESTOS CEMENT
PE
LDPE
HDPE
PVDF
PTFE
PA
PP
GLASS PYREX
OTHER
Factory setting:
STAINLESS STEEL
SOUND VELOCITY
Use this function to display the sound velocity in the pipe material.
PIPE
The sound velocity in the pipe must be specified.
User input:
Fixed-point number 800 to 6500 m/s
Factory setting:
3120 m/s
CIRCUMFERENCE
Use this function to display the pipe outer circumference.
The pipe outer circumference or the pipe diameter must be specified.
User input:
Fixed point number 31.4 to 15,700.0 mm
Factory setting:
279.3 mm
PIPE DIAMETER
Use this function to display the pipe outer diameter.
The pipe outer diameter or the pipe circumference must be specified.
User input:
Fixed-point number 10.0 to 5000.0 mm
Factory setting:
88.9 mm
Functional description PIPE DATA