Proline Prosonic Flow 91
Endress+Hauser
4.
Fit the sensor holders over the individual mounting bolts and tighten securely with the
retaining nut.
Fig. 17:
Mounting the sensor holders
5.
Coat the contact surfaces of the sensors with an even layer of coupling fluid approx. 1 mm
thick, going from the groove through the center to the opposite edge.
Fig. 18:
Coating the contact surfaces of the sensor with coupling fluid
6.
Insert the sensor into the sensor holder.
7.
Fit the sensor cover on the sensor holder and turn until:
– The sensor cover engages with a click
– The arrows (Å / Æ "close") are pointing towards one another.
8.
Screw the connecting cable into the individual sensor.
Fig. 19:
Mounting the sensor and connecting the connecting cable
This completes the mounting process. The sensors can now be connected to the transmitter via the
connecting cables → ä 22.
Installation
A0001117
A0011373
A0011376
19