11.11 Group SENSOR DATA

All sensor data (calibration factors, zero point and nominal diameter etc.) are set at the factory.
"
Caution!
Under normal circumstances you should not change the following parameter settings, because changes
affect numerous functions of the entire measuring facility in general and the accuracy of the measuring
system in particular. Therefore, the functions described below are provided with an additional prompt (with
the code 10) once you enter your private code.
K-FACTOR
Use this function to display the current calibration factor (positive and negative flow
direction) for the sensor. The calibration factor is determined and set at the factory.
User input:
5-digit fixed-point number: 0.5000 ...2.0000
Factory setting:
Depends on nominal diameter and calibration
!
This value is also provided on the sensor nameplate.
ZERO POINT
This function shows the current zero-point correction value for the sensor.
Zero-point correction is determined and set at the factory.
User input:
Max. 4-digit number: -1000...+1000
Factory setting:
Depends on nominal diameter and calibration
!
This value is also provided on the sensor nameplate.
NOMINAL DIAMETER
This function shows the nominal diameter for the sensor. The nominal diameter depends
on the size of the sensor and is set at the factory.
Options:
2...2000 mm
1/12...78"
Factory setting:
Depends on the size of the sensor
!
This value is also provided on the sensor nameplate.
MEASURING PERIOD
Use this function to set the time for a full measuring period. The duration of the measuring
period is calculated from the rise time of the magnetic field, the brief recovery time, the
(automatically tracked) integration time and the empty pipe detection time.
User input:
10...1000 ms
Factory setting:
Depends on nominal diameter
EPD ELECTRODE
Indicates whether the sensor is equipped with an EPD electrode.
Display:
YES
NO
Factory setting:
YES → Electrode fitted as standard
Functional description SENSOR DATA
Note!
Note!
Note!
Appendix
103