Description of device functions
74
T-DAT SAVE/LOAD
In this function, the configuration/settings of the transmitter can be saved to a
transmitter DAT (T-DAT) or uploading a configuration from the T-DAT to the EEPROM
can be activated (manual back-up function).
Application examples:
• After commissioning, the current measuring point parameters can be saved to the
T-DAT (backup).
• When exchanging the transmitter, the data can be loaded from the T-DAT to the new
transmitter (EEPROM).
Options:
CANCEL
SAVE (from EEPROM to T-DAT)
LOAD (from the T-DAT to the EEPROM)
Factory setting:
CANCEL
!
• If the target device has an older software version, the message "TRANSM. SWDAT" is
displayed during startup. Then only the SAVE function is available.
• LOAD
This function is only possible if the target device has the same software version as, or a
more recent software version than, the source device.
• SAVE
This function is always available.
Functional description OPERATION
Note!
Proline Prosonic Flow 91
Endress+Hauser