Group Sensor Data; Function Group Configuration - Endress+Hauser Proline Promass 83 Function Manual

Modbus rs485 coriolis mass flow measuring system
Hide thumbs Also See for Proline Promass 83:
Table of Contents

Advertisement

Device Functions Proline Promass 83 MODBUS RS485
Endress+Hauser
9.4

Group SENSOR DATA

9.4.1

Function group CONFIGURATION

BASIC FUNCTION
G
BASIC FUNCTION → SENSOR DATA → CONFIGURATION
All sensor data (calibration factor, zero point and nominal diameter) are set at the factory and saved on the S-DAT sensor
memory chip.
"
Caution!
Under normal circumstances you should not change the following parameter settings, because changes affect numerous
functions of the entire measuring facility in general and the accuracy of the measuring system in particular. For this
reason, the functions described below cannot be changed even when you enter your personal code.
Contact the Endress+Hauser service organization if you have any questions about these functions.
!
Note!
The individual values of the functions are also provided on the sensor nameplate.
K-FACTOR
6800
MODBUS register:
7513
Data type:
Float
Access:
read
ZERO POINT
6803
MODBUS register:
7527
Data type:
Float
Access:
read/write
NOMINAL
6804
DIAMETER
MODBUS register:
mm
7525
inch
7526
Data type:
Integer
Access:
read
MODBUS RS485
GDA
PROCESS PARAMETER
GIA
SYSTEM PARAMETER
GLA
SENSOR DATA
GNA
Function description
This function shows the current calibration factor for the sensor.
Factory setting: Depends on nominal diameter and calibration
This function shows the current zero point correction value for the sensor.
Display: max. 5-digit number: -99999 to +99999
Factory setting: Depends on calibration
Display: Nominal diameter for the sensor
0 = DN 1 or 1/24"
1 = DN 2 or 1/12"
2 = DN 3 or 1/8"
3 = DN 3.5 or 9/64"
4 = DN 4 or 5/32"
5 = DN 6 or 1/4"
6 = DN 8 or 5/16"
7 = DN 10 or 3/8"
8 = DN 15 or 1/2"
9 = DN 15 FB or 1/2" FB (FB = full bore)
10 = DN 20 or 3/4"
11 = DN 25 or 1"
12 = DN 25 FB or 1" FB
13 = DN 32 or 1 1/4"
14 = DN 40 or 1 1/2"
15 = DN 40 FB or 1 1/2" FB
16 = DN 50 or 2"
17 = DN 50 FB or 2" FB
18 = DN 65 or 2 1/2"
19 = DN 80 or 3"
20 = DN 100 or 4"
21 = DN 125 or 5"
22 = DN 150 or 6"
23 = DN 200 or 8"
24 = DN 250 or 10"
9 Block BASIC FUNCTION
CONFIGURATION
680
119