Introduction; General Description; General Specifications; General Technical Specifications - Teletek electronics REPEATER Installation And Programming Manual

Intelligent interactive fire alarm control panel
Table of Contents

Advertisement

Repeater – Installation and Programming Manual

1. INTRODUCTION

1.1. General Description

The Repeater is a device that duplicates the information provided by the Simpo, Iris and Iris Pro addressable fire
panels in order to help you get information on the current situation in the premises without having to be physically
close to the main panel.
The connection between the repeating panel and the main panels has been obtained by
using a redundant network module based on the RS485 interface. The monitoring information is displayed on the
LCD display. There is also LED indication available.
To avoid or significantly diminish problems when mounting the system it must be carefully planned prior

1.2. General Specifications

The front panel consists of LCD module, functional buttons and system status LED indication. Separate access
level passwords provide access to the functions of the panel. The panel has a built-in real time clock and calendar,
allowing day and night time modes of work. Switching over between the two modes can be automatic or manual.
Events like FIRE, RESET, FAULT, etc., are saved i n the memory, thereby creating an event log-file. It contains
the time and date, the address of the device, the name of the device, the zone number, the name of the zone, etc.
1.2.1. General Technical Characteristics:
Power Supply: (24 ± 4) VDC
Max. consumption: 0.11A
Communication - RS485
Twisted pair cable:
- Length - max. 1000m (between repeater - fire panel)
- Cross Section - 0.5 - 2.5mm2
ATTENTION!
Operation with the Repeater Panel
is supported for the following revisions:
IRIS Fire Alarm Panel
LCD PCB Hardware revision: 2.4 and higher
MAIN Board Firmware revision: 4.2 and higher
SIMPO Fire Alarm Panel
MAIN Board Firmware revision: 2.8 and higher
1.2.2. Description of the terminal rows

1.2.2 Environment

• Degree of protection: IP30
• Operation temperature: -5ºС up to +40ºC
• Relative humidity: up to 95% (without condense)
• Storage temperature: -10ºС up to +60ºC
• Weight (without the battery): ~ 0.5 kg
ATTENTION: Do not install the fire panel near power electromagnetic fields (radio equipment,
electric motors, etc.)
to installation.
Loop IN - Connect the input line for communication
Loop OUT - Connect the output line for
communication.
Power Supply - Power supply for the repeater panel:
- Use external 24VDC power supply unit;
- Use the AUX output of the fire alarm panel.
Micro USB - Micro USB input for programming and
firmware update.