Table 38: Behavior In The Event Of An I/O Module Error Dependent On The - WAGO 750 Series Manual

4ai u/i diff galv 4-channel analog input; for voltage/current
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

66
Diagnostics
Table 38: Behavior in the Event of an I/O Module Error Dependent on the Configuration
Configuration
Wire break/ /
overload
monitoring*
OFF
OFF
ON
ON
*The monitoring must be activated separately or deactivated
The limiting values for detecting an underrange / overrange, a wire break or an
overload and the output process values are specified in the process image tables
(see section "Process Image").
A general error signals a diagnosed error status. A general error is displayed if
one of the error statuses named in this section occur. If there are any of the
diagnostics for range violation, overload or wire break, the bit for general error is
always set.
Manual
Version 1.0.0
I/O module behavior
Underrange/
for wire break/
overrange
overload
monitoring
Process value is
saturated,
OFF
no change in statues
byte,
error LED off
Process value is
saturated,
(bit 0: Underrange or bit
1: Overrange /
ON
Overload) is set,
general error (bit 6:
General Error) is set,
error LED ON
Process value is
saturated,
error bit (bit 4: Overload
OFF
or bit 5: Wire break) is
set, general error (bit 6:
General Error) is set,
error LED ON
Process value is
saturated,
error bit (bit 4: Overload
or bit 5: Wire break) is
ON
set, general error (bit 6:
General Error) is set,
error LED ON
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
I/O module behavior
for range violation
Process value is
saturated,
no change in statues
byte,
error LED off
Process value is
saturated,
error bit (bit 0:
Underrange or bit 1:
Overrange) is set,
general error (bit 6:
General Error) is set,
error LED ON
Process value is
saturated,
no change in statues
byte,
error LED off
Process value is
saturated,
error bit (bit 0:
Underrange or bit 1:
Overrange) is set,
general error (bit 6:
General Error) is set,
error LED ON