Figure 21: Offset Correction; Figure 22: Gain Correction - WAGO 750 Series Manual

4ai u/i diff galv 4-channel analog input; for voltage/current
Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

62
Commissioning
The calibration process is independent of the set signal type!
User calibration follows the same principle as the current and voltage
measurement. The content of the dialog windows differs accordingly!
1.
To select the process value for the respective channel, select the
corresponding tab [Channel 1] ... [Channel 4].
Select the control field [User calibration].
2.
3.
Click the [Start Calibration] button.
4.
Follow the instructions in the dialog windows that open:

Figure 21: Offset Correction

Figure 22: Gain Correction

5.
If necessary, repeat the calibration for each channel.
For the gain correction, an arbitrary reference value within the measurement
range can be entered as a setpoint. Ideally, the value should be as close as
possible to the upper end of the range (about 9 V, 190 mV or 19 mA). Having the
process value set to 10 V, 200 mV or 20 mA by an extremely faulty calibration
should be avoided.
After the calibration, the process values will correspond to the reference values
over the entire range.
The measuring circuits can be calibrated independently in the same way.
Manual
Version 1.0.0
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-471

Table of Contents