Diagnostics

9.1

Serial Operating Modes RS-232, RS-422 and RS-485

Table 50: Diagnostics, Serial Operating Modes RS-232, RS-422 and RS-485

Diagnostics
Input buffer full
Output buffer
full
Parity error
Overflow
9.2

DMX Operating Mode

Table 51: Diagnostics, DMX Operating Mode

Diagnostics
Transmission
failure when
receiving
Packet ID
Event
The I/O module receives
data via the serial interface
faster than accepted by the
application.
The I/O module receives
data faster from the
application than it sends via
the serial interface.
Data transmission was
interrupted.
Data loss has occurred.
Event
More than 1.2 s has passed
since receipt of a valid
packet.
The start code of the
received DMX packet is
not 0.
Diagnostics
Solution
Make sure that the application
always accepts data
immediately.
Reduce data traffic.
Use flow control.
Reduce baud rate.
Check "Continuous Send".
Reduce data traffic.
Increase baud rate.
Make sure that the opposite
side accepts data.
Check the configuration of the
interface parameters.
Use a shielded cable.
Change wire routing.
Shorten cable.
Eliminate interference.
Reduce baud rate.
Solution
Check wire routing.
Check cable type.
Check DMX sender operation.
Check wire routing.
Check cable type.
Check the start code of the
DMX sender.
Increase the number of
transmitting DMX channels
(min. 27 channels).