VAT 650 Series Installation, Operating, & Maintenance Instructions page 9

Pendulum control & isolation valve with cc-link interface with valve cluster functionality
Table of Contents

Advertisement

1.
Install valves [1] into the vacuum system. Valve seat side should face process chamber. The valve seat side is
indicated by the symbol "∇" on the valve flange.
Caution: Do not tighten the flange screws stronger than indicated under «Tightening torque».
Caution: Do not admit higher forces to the valve than indicated under «Admissible forces».
Note: Make sure that enough space is kept free to do preventive maintenance work. The required space is indicated
on the dimensional drawing.
2.
Install the ground connection cable at controller. Refer to «Electrical connection»
3.
Connect compressed air supply to connection labeled 'IN' located at actuator, see Figure 1 below.
Connect compressed air return line connection labeled 'OUT' located at actuator, see Figure 1 below.
Caution: Compressed air pressure must be in the range of: 4 - 7 bar / 55 - 100 psi (above ATM).
Note: Use only clean, dry or slightly oiled air. IN / OUT connections are 1/8" ISO/NPT internal threads.
4.
Install pressure sensor(s) [2] according to the recommendations of the sensor manufacturer and directives given
under
«Requirements to sensor connection».
Note: Input for second sensor is available on 650 . . - . . . N versions.
5.
Connect sensor cable [3] to sensor(s) and then to Master valve (connector: SENSOR).
Refer to chapter «Electrical connection» for correct wiring.
6.
Connect Master valve to CC-Link [4] (connector: INTERFACE). Refer to «CC-Link schematics» for correct wiring.
7.
Enable terminating resistor in link adapter of first and last valve in the system. Refer to «Valve cluster connection» for
details.
8.
Connect link cable [6] between Slave valve(s) and Master valve (link adapter). Refer to «Valve cluster connection» for
correct wiring.
9.
Connect power supply [5] to each valve (connector: POWER). Refer to chapter «Electrical connection» for correct
wiring.
Note: To provide power to the valve motor pins 4 and 8 must be bridged, otherwise motor interlock is active and the
valve enters the safety mode and is not operative. Refer also to «Safety mode».
10. This valve has a double sealed rotary feedthrough and optionally an intermediate pumping port for the actuator shaft.
This port (1/8" ISO/NPT) could be connected to the vacuum line, see Figure 2 below.
11. These valves may optionally be equipped with a heating device. Connect VAT heating device according to manual of
respective heating device.
12. Perform «Setup procedure» to prepare valve cluster for operation.
Note: Without performing the setup procedure the valve cluster will not be able to do pressure control.
OUT
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4" - 10"), CC-Link
Fig. 1
IN
intermediate
pumping port
Fig. 2
280672EB
9/94
2010-12-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents