VAT 651 Series Installation, Operating,  & Maintenance Instructions

VAT 651 Series Installation, Operating, & Maintenance Instructions

Table of Contents

Advertisement

Quick Links

Installation, Operating &
Maintenance Instructions
Pendulum control & isolation valve
with extended control range
with Logic interface
Series 651
DN 160–250 mm (I.D. 6" - 10")
This manual is valid for the valve ordering number(s):
651 . . - . .GC- . . . .
651 . . - . .GE- . . . .
651 . . - . .AC- . . . .
651 . . - . .AE- . . . .
651 . . - . .HC- . . . .
651 . . - . .HE- . . . .
651 . . - . .CC- . . . .
651 . . - . .CE- . . . .
SPS = Sensor Power Supply
configured with firmware 600P.1G.00.04, 600P.1G.00.05...08
Sample picture
605451EC
(1 sensor input)
(2 sensor inputs)
(1 sensor input / ±15V SPS)
(2 sensor inputs / ±15V SPS)
(1 sensor input / PFO)
(2 sensor inputs / PFO)
(1 sensor input / ±15V SPS / PFO)
(2 sensor inputs / ±15V SPS / PFO)
PFO = Power Failure Option
Edition 2014-07-10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 651 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for VAT 651 Series

  • Page 1 Installation, Operating & Maintenance Instructions Pendulum control & isolation valve with extended control range with Logic interface Series 651 DN 160–250 mm (I.D. 6“ - 10") This manual is valid for the valve ordering number(s): 651 . . - . .GC- ..(1 sensor input) 651 .
  • Page 2 The VAT firmware may not be used for purposes other than those intended nor is it permitted to make copies of the VAT firmware. In particular, it is strictly forbidden to give copies of the VAT firmware to other people.
  • Page 3: Table Of Contents

    Series 651 Contents Description of product ................ 5 Identification of product ....................5 Use of product ......................... 5 Used abbreviations ......................5 Related documents......................5 Important information....................... 5 Technical data ......................... 6 1.6.1 Control and actuating unit ................. 6 1.6.2 Valve unit ......................
  • Page 4 Series 651 4.6.2 Tuning of pressure control performance with fixed PI control ......56 4.6.3 Tuning of pressure control with soft pump ............59 Operation ................... 62 Normal operation ......................62 5.1.1 Local operation ....................63 5.1.2 Remote operation .................... 64 Close valve ........................
  • Page 5: Description Of Product

    This product is a throttling pendulum valve with isolation functionality. It is intended to use for downstream pressure control applications. Use product for clean and dry vacuum applications only. Other applications are only allowed with the written permission of VAT. Used abbreviations Abbreviation...
  • Page 6: Technical Data

    DESCRIPTION OF PRODUCT Series 651 Technical data 1.6.1 Control and actuating unit Description Power input (α) +24 VDC (±10%) @ 0.5 V pk- [connector: POWER] pk max. [651 . . - . . A . - ../ 651 . . - . . G . - ..] 50 W max.
  • Page 7 Series 651 DESCRIPTION OF PRODUCT Description (continuation) Sensor input Signal input voltage 0-10 VDC / Ri>100 kΩ [connector: SENSOR] ADC resolution 0.23 mV Sampling time 10 ms Digital inputs ±24 VDC max. [connector: INTERFACE] Digital outputs [connector: INTERFACE] Input voltage 70 VDC or 70 V peak max.
  • Page 8: Valve Unit

    DESCRIPTION OF PRODUCT Series 651 1.6.2 Valve unit Description Pressure range at 20°C - Aluminum 1 × 10E-8 mbar to 1.2 bar (abs) (651 . . - . A . . - ..) - Aluminum hard anodized 1 ×...
  • Page 9 Series 651 DESCRIPTION OF PRODUCT Description ® - Seals Viton (standard). Other materials available. Seal materials are declared on dimensional drawing of specific valve ordering number. DN 160 DN 200 DN 250 6" 8" 10" (65144 - ..) (65146 - ..) (65148 - ..) Max.
  • Page 10: Safety

    SAFETY Series 651 Safety Compulsory reading material Read this chapter prior to performing any work with or on the product. It contains important information that is significant for your own personal safety. This chapter must have been read and understood by all persons who perform any kind of work with or on the product during any stage of its serviceable life.
  • Page 11: Personnel Qualifications

    Series 651 SAFETY Personnel qualifications WARNING Unqualified personnel Inappropriate handling may cause serious injury or property damage. Only qualified personnel are allowed to carry out the described work. Safety labels Label Part No. Location on valve On protective foil covering of T-9001-156 valve opening 605451EC...
  • Page 12: Design And Function

    DESIGN AND FUNCTION Series 651 Design and Function Design Plate seal Integrated controller Body seal Rotary feed through seals Shaft feed through seals Pendulum plate Bonnet seal Sealing ring Actuator 12/99 Edition 2014-07-10 605451EC...
  • Page 13: Function

    Series 651 DESIGN AND FUNCTION Function The valve plate acts, due to its pendulum motion, as a throttling element and varies the conductance of the valve opening. The integrated controller calculates the required plate position to achieve the set point pressure. Actuation is performed by a stepper motor. An encoder monitors the position. This principle ensures fast and accurate process pressure control.
  • Page 14: Pressure Control System Overview And Function

    DESIGN AND FUNCTION Series 651 3.2.1 Pressure control system overview and function Vacuum pressures are always absolute pressures unless explicitly specified as pressure differences. Valve Process chamber Gas inlet Pressure sensor(s) Sensor cable Controller and actuator Seff Cable to remote control unit Cable to power supply HV Pump Q / p...
  • Page 15: Principle Of A Pressure Control System

    Series 651 DESIGN AND FUNCTION 3.2.1.1 Way of operation The controller compares the actual pressure in the process chamber given by the pressure sensor with the preset pressure. The controller uses the difference between actual and set pressure to calculate the correct position of the control valve. The controller drives the control valve into the correct position and the actual pressure again equals the set pressure.
  • Page 16: Installation

    Make sure that the supplied products are in accordance with your order. • Inspect the quality of the supplied products visually. If it does not meet your requirements, please contact VAT immediately. • Store the original packaging material. It may be useful if products must be returned to VAT.
  • Page 17: Installation Into The System

    Series 651 INSTALLATION Installation into the system WARNING Valve opening Risk of serious injury. Human body parts must be kept out of the valve opening and away from moving parts. Do not connect the controller to power before the valve is installed complete into the system.
  • Page 18: Installation Space Condition

    INSTALLATION Series 651 Mount valve to a clean system only. 4.2.1 Installation space condition Install the valve with integrated controller with space for dismantling and air circulation as shown in figure below. 100 mm 50 mm 18/99 Edition 2014-07-10 605451EC...
  • Page 19: Connection Overview

    Series 651 INSTALLATION 4.2.2 Connection overview System: Valve Process chamber Gas inlet Pressure sensor(s) Sensor cable(s) Controller and actuator Cable to remote control unit Cable to power supply Pump Controller: 4.2.3 Installation procedure 1. Install valve [1] into the vacuum system. Valve seat side should face process chamber. The valve seat side is indicated by the symbol "∇"...
  • Page 20 8. This valve has a double sealed rotary feedthrough and optionally an intermediate pumping port for the actuator shaft. This port (1/8“ ISO/NPT) could be connected to the vacuum line, see Figure 2 below. 9. This valve may optionally be equipped with a heating device. Connect VAT heating device according to manual of respective heating device.
  • Page 21: Tightening Torque

    Series 651 INSTALLATION Tightening torque The torque values below are dependent on many factors, such as materials involved, surface quality, surface treatment, and lubrication. The torques below are valid if immersion depth of the mounting screws is at least once the thread diameter (min. 1d), and the friction coefficient of the screw-flange + µ...
  • Page 22: Mounting With O-Ring In Grooves

    (65148 - ..- ..) For a combination of both forces (F and M) the values are invalid. Verify that the depth of the mounting screws is min. 1 x thread diameter. Please contact VAT for more information. 22/99 Edition 2014-07-10 605451EC...
  • Page 23: Requirements To Sensor Connection

    Series 651 INSTALLATION 4.3.4 Requirements to sensor connection To achieve fast and accurate pressure control a fast sensor response is required. Sensor response time: < 50ms. The sensor is normally connected to the chamber by a pipe. To maintain that the response time is not degraded by this connection it needs to meet the following requirements: •...
  • Page 24: Ground Connection

    INSTALLATION Series 651 4.4.1 Ground connection Recommendation for ground strap between controller and system chassis. ∅ ∅ ∅ ∅ ∅ ∅ ∅ ∅ Material B1 (min.) B2 (min.) d1 ( d2 ( (Length max.) copper tinned 200 mm 25 mm 25 mm 4.5 mm customized...
  • Page 25: Sensor Supply Concepts

    Series 651 INSTALLATION 4.4.2 Sensor supply concepts This valve offers 3 alternative concepts to supply the sensor(s) with power. This depends on the sensor type and valve version that is used. This valve is available with an optional sensor power supply module (SPS) that converts ±15 VDC from the 24 VDC.
  • Page 26: Power And Sensor Connection (+24 Vdc Sensors)

    INSTALLATION Series 651 4.4.3 Power and sensor connection (+24 VDC sensors) [651 . . - . . G . - ../ 651 . . - . . H . - ..versions recommended] 4.4.3.1 Sensor power wiring via controller Pins 4 and 8 must be...
  • Page 27 Series 651 INSTALLATION 4.4.3.2 Sensor power wiring external Pins 4 and 8 must be bridged for operation. An optional switch would allow for motor interlock to prevent valve from moving. Low range sensor may be connected to sensor 1 or sensor 2 input.
  • Page 28: Power And Sensor Connection (±15 Vdc Sensors) Without Opt. Sps Module

    INSTALLATION Series 651 Power and sensor connection (± ± ± ± 15 VDC sensors) without opt. SPS module 4.4.4 [651 . . - . . G . - ../ 651 . . - . . H . - ..versions only] 4.4.4.1 Sensor power wiring via controller Pins 4 and 8 must be...
  • Page 29 Series 651 INSTALLATION 4.4.4.2 Sensor power wiring external Pins 4 and 8 must be bridged for operation. An optional switch would allow for motor interlock to prevent valve from moving. Low range sensor may be connected to sensor 1 or sensor 2 input.
  • Page 30: Power And Sensor Connection (±15 Vdc Sensors) With Optional Sps Module

    INSTALLATION Series 651 Power and sensor connection (± ± ± ± 15 VDC sensors) with optional SPS module 4.4.5 [651 . . - . . A . - ../ 651 . . - . . C . - ..versions only] Pins 4 and 8 must be bridged for operation.
  • Page 31: Service Port Connection

    You can use our Software (freeware) 'Control Performance Analyzer' which can be downloaded from: http://www.vatvalve.com/customer-service/informations-and-downloads/control-performance-analyzer. Alternatively the VAT Service Box2 can be connected to the service port for setup and local operation. The service port is not galvanic isolated. Therefore we recommend using this only for setup, testing and maintenance and not for permanent control.
  • Page 32: Functions And Wiring

    INSTALLATION Series 651 4.4.7 Functions and Wiring Logic interface allows for remote operation by means of digital and analog signals. Digital inputs may be operated either by switches or by voltage sources. a) Configuration with switches for digital inputs: SC1096 A Do not connect other pins than indicated in the schematics above! Use only screws with 4-40UNC thread for fastening the DB-25 connector! 32/99...
  • Page 33 Series 651 INSTALLATION a) Configuration with voltage source for digital inputs: SC1097A Do not connect other pins than indicated in the schematics above! Use only screws with 4-40UNC thread for fastening the DB-25 connector! 605451EC Edition 2014-07-10 33/99...
  • Page 34: Digital Inputs

    INSTALLATION Series 651 4.4.8 Digital inputs Function Signal Description Priority type This pin selects the control mode. This valve may either be operated as pressure controller or as position controller. PRESSURE CONTROL is activated as long as optocoupler is ‘on’. CONTROL Digital The PID controller controls the chamber pressure according to...
  • Page 35 Series 651 INSTALLATION Function Signal Description Priority type This function compensates the pressure gauge offset voltage and sets the pressure value to zero. In case of a 2 sensor system both sensor inputs will be adjusted. This function is initiated by the ‘off’ to ‘on’ transition of the optocoupler.
  • Page 36: Digital Outputs

    INSTALLATION Series 651 4.4.9 Digital outputs Function Signal Description type This output is active in all operation modes and indicates either that the valve is open or that a service is requested. VALVE A service request is indicated when the valve requires cleaning due OPEN Digital to contamination.
  • Page 37: Analog Inputs And Outputs

    Series 651 INSTALLATION 4.4.10 Analog inputs and outputs Function Signal Description type The meaning of the setpoint input depends on the operation mode. LEARN: A voltage of 0-10V shall be applied to this input as pressure limit for learn. The limit pressure is in linear relation to the applied voltage. 10V relates to sensor full scale.
  • Page 38: Initial Operation

    For ease setup (in Local mode) of ‘Interface’, ‘Valve’, ‘Sensor’, ‘Senor ZERO’, ‘LEARN’ and ‘PRESSURE CONTROL COFIGURATION’ it is possible to use the CPA 3.0, The free download is available on the VAT homepage: http://www.vatvalve.com/customer- service/informations-and-downloads/control-performance-analyzer 4.5.2 Logic Interface configuration Interface configuration must be adapted according to application needs.
  • Page 39: Valve Configuration

    Series 651 INSTALLATION Local operation: Remote operation: (‘Control Performance Analyzer’ or ‘Service Box 2‘) • With CPA, do configuration in menu ‘Interface / Setup’. It’s not possible to do ‘Interface • configuration‘ via remote operation. With SB2, do configuration in menu ‘Setup / Interface’.
  • Page 40: Sensor Configuration

    INSTALLATION Series 651 4.5.4 Sensor configuration Basic sensor configuration must be adapted according to application needs. • ZERO function: This may be ‘disabled’ or ‘enabled’. Default is ‘enabled‘. Refer also to chapter «ZERO». • Sensor configuration with 2 sensor version [651 . . - . . . E - ..]. Refer also to chapter: «Pressure control operation with 2 sensors».
  • Page 41: Learn (Adaptive)

    Series 651 INSTALLATION 4.5.1 LEARN (adaptive) LEARN adapts the PID controller of the valve to the vacuum system and its operating conditions. LEARN must be executed only once during system setup. The LEARN routine determines the characteristic of the vacuum system. Based on this, the PID controller is able to run fast and accurate pressure control cycles.
  • Page 42 INSTALLATION Series 651 Gasflow calculation for LEARN: Do not apply a different gasflow for learn than determined below. Otherwise pressure control performance may be insufficient. Required pressure / flow regime must be known to calculate the most suitable learn gas flow for a specific application. 1.
  • Page 43: Pressure Control Configuration

    Series 651 INSTALLATION 4.5.2 Pressure control configuration Select the configuration what your application needs. Constant gas flow available Constant gas flow not System Configuration available Tv*<= 500 sec Tv* > 500 sec Downstream Adaptive pressure Process controller Fixed pressure controller chamber (Refer to chapter: (Refer to chapter: Pressure controller)
  • Page 44 3 = Soft pump For easy setup (Local operation) of ‘Pressure controller’ and ‘Pressure control parameter’ please use the VAT “Control Performance Analyzer” CPA 3.0. There is a free download on the VAT home page, refer to: http://www.vatvalve.com/customer- service/informations-and-downloads/control-performance-analyzer 4.5.2.2 With CPA 3.0 direct setup (standard)
  • Page 45 Series 651 INSTALLATION 4.5.2.3 Pressure control parameter Local operation: Remote operation: (‘Control View’ or ‘Control Performance Analyzer’) • Open CV or CPA • Go to «Tools» > «Terminal» and send setup command s:02 according to application needs. (possibility of adjustment see below) Acknowledgement Command (within 10ms after reception of...
  • Page 46: Pressure Control Algorithem

    INSTALLATION Series 651 4.5.3 Pressure control algorithem • Local operation only: With CPA direct setup, see chapter: With CPA 3.0 direct setup (standard). With CPA, go to «Tools» > «Terminal» and send setup commands according to application needs. See next tables. 4.5.3.1 Adaptive control algorithm (downstream) Parameter...
  • Page 47 Series 651 INSTALLATION GAIN FACTOR The GAIN FACOTR is a control parameter to adapt the performance of the pressure control algorithm. A higher gain results in faster response, higher over- / undershoot of pressure. A lower gain results in slower response, lower over- / undershoot of pressure.
  • Page 48 INSTALLATION Series 651 4.5.3.2 Fixed 1 control algorithm Parameter Command Request Data Type Values s:02B01c s:02 c = 0.00…1 000.0 ’ ’ RAMP TIME FLOAT Default is: 0.00 i:02B01 i:02B01c c = 0 or 1 s:02B02c s:02 0 = constant time RAMP MODE UINT 1 = constant slope...
  • Page 49 Series 651 INSTALLATION Example: Set RAMP MODE of the Fixed 1 pressure controller to the value 0 (fixed time) Command Pressure Parameter selection variable Parameter value controller s:02 B (a) 02 (bb) 0 (c) s:02B020 To optimize Fixed 1 algorithm, refer to chapter «Tuning of control performance». 4.5.3.3 Fixed 2 control algorithm Parameter...
  • Page 50: Tuning Of Control Performance

    INSTALLATION Series 651 4.5.3.4 Soft pump control algorithm Parameter Command Request Data Type Values s:02D01c s:02 c = 0.00…1 000.0 ’ ’ RAMP TIME FLOAT Default is: 0.00 i:02D01 i:02D01c s:02D02c c = 0…1 s:02 0 = constant time RAMP MODE UINT 1 = constant slope i:02D02...
  • Page 51: Tuning Of Pressure Control (Adaptive)

    Pressure / flow / gas conditions to be controlled • Chamber volume • Pumping speed (l/s) and pump type (e.g. turbo pump) • System description • Problem description Send diagnostic file with and all required information to tuning-support@vat.ch 605451EC Edition 2014-07-10 51/99...
  • Page 52 INSTALLATION Series 651 4.6.1.1 Gain factor adjustment The gain factor effects: Stability, Response time Default value is 1. Adjustment range is from 0.0001 to 7.5. Higher gain results in: faster response higher over- / undershoot of pressure Lower gain results in: slower response lower over- / undershoot of pressure Adjustment procedure:...
  • Page 53 Series 651 INSTALLATION 4.6.1.2 Sensor delay adjustment Sensor delay adjustment effects: Stability Default value is 0sensorDeay0. Adjustment range is from 0 to 1.0s. Pipes and orifices for sensor attachment delay response time and so badly impact pressure control stability. By adapting this parameter to the approximate delay time stability problems can be reduced. But control response time will be slowed down by this measure.
  • Page 54 INSTALLATION Series 651 4.6.1.3 Setpoint ramp adjustment Setpoint ramp effects: Undershoot of pressure, Response time Default value for Setpoint Ramp is 0. Adjustment range for Setpoint Ramp is from 0 to 10 s. This parameter defines the time that is used to decrease / raise pressure between 2 setpoints. Especially in pressure decrease situations at low flows pressure response can be improved much by adapting setpoint ramp time.
  • Page 55 Series 651 INSTALLATION 4.6.1.4 Valve speed adjustment Valve speed effects: Response time Default value is 1000. Adjustment range is from 1 to 1000. This parameter effects valve plate actuating speed. Speed adjustment is effective for PRESSURE CONTROL and POSITION CONTROL. Normally best pressure control response is achieved with max.
  • Page 56: Tuning Of Pressure Control Performance With Fixed Pi Control

    INSTALLATION Series 651 4.6.2 Tuning of pressure control performance with fixed PI control 4.6.2.1 Optimizing P gain and I gain This valve may be used for downstream or upstream pressure control depending on configuration. The PI parameters of the pressure controller require correct adjustment. These parameters must be set once during system setup and are stored in the device memory which is power fail save.
  • Page 57 Series 651 INSTALLATION Optimizing P gain While optimizing P gain, the gas flow determined above has to be constant all the time. Start optimization with P gain set to 1.0 and I gain set to 0.0. Set chamber pressure to SP2, wait until the pressure is stable. Set pressure to SP1. If the transition from SP2 to SP1 results in a significant pressure over shoot or even does not stabilize at all, the P gain is too high.
  • Page 58 Pressure / flow / gas conditions to be controlled • Chamber volume • Pumping speed (l/s) and pump type (e.g. turbo pump) • System description • Problem description Send diagnostic file with and all required information to tuning-support@vat.ch 58/99 Edition 2014-07-10 605451EC...
  • Page 59: Tuning Of Pressure Control With Soft Pump

    The VAT soft pump controller requires a pump down time shorter than 10 sec. for good control results. If the required pump down time is longer than 10 sec., the pump down curve has to be partitioned into sections shorter than 10 sec.
  • Page 60 INSTALLATION Series 651 Optimizing P gain WE start by setting the P gain to 1.0 as a trial value and adjust according to the response. The pump down routine has to be controlled as follows: Move control valve into close position Start pump down by opening the pump isolation valve or starting the pump and sending the first pressure set point to the valve controller.
  • Page 61 Pressure / flow / gas conditions to be controlled • Chamber volume • Pumping speed (l/s) and pump type (e.g. turbo pump) • System description • Problem description Send diagnostic file with and all required information to tuning-support@vat.ch 605451EC Edition 2014-07-10 61/99...
  • Page 62: Operation

    OPERATION Series 651 Operation WARNING Unqualified personnel Inappropriate handling may cause serious injury or property damage. Only qualified personnel are allowed to carry out the described work. WARNING Valve opening Risk of serious injury. Human body parts must be kept out of the valve opening and away from moving parts. Do not connect the controller to power before the valve is installed complete into the system.
  • Page 63: Local Operation

    Local operation means that the valve is operated via the service port using a computer or the Service Box 2. When using a computer, a service cable and a software from VAT is required. You can use our Software (freeware) 'Control Performance Analyzer' which can be downloaded from: http://www.vatvalve.com/customer-service/informations-and-downloads/control-performance-analyzer.
  • Page 64: Remote Operation

    OPERATION Series 651 5.1.2 Remote operation This product is equipped with a Logic interface to allow for remote operation. See section «Logic interface» for details. 'Control Performance Analyzer' software or 'Service Box 2' may be used for monitoring during remote control. 'Control Performance Analyzer' software 'Service Box 2' In case ‘Control Performance Analyzer’...
  • Page 65: Close Valve

    Series 651 OPERATION Close valve Local operation: Remote operation: (‘Control View’, ‘Control Performance Analyzer’ or (Refer to chapter «Digital inputs» for details) ‘Service Box 2‘) Push CLOSE button Send CLOSE VALVE Open valve Local operation: Remote operation: (‘Control View’, ‘Control Performance Analyzer’ or (Refer to chapter «Digital inputs»...
  • Page 66: Operation With 2 Sensors

    OPERATION Series 651 5.5.1 Operation with 2 sensors [applicable with 612 . . - . . . E - ..version only] If 2 sensor operation is enabled, changeover between the sensors is done automatically during pressure control.
  • Page 67: Display Information

    Series 651 OPERATION Display information There is a 4 digit display located on the panel. It displays configuration, status and position information. For details refer to following tables. 1 2 3 4 Display 5.6.1 Power up Description Digit 1 Digit 2 Digit 3 Digit 4 ●...
  • Page 68: Operation

    OPERATION Series 651 5.6.2 Operation Description / Mode Digit 1 Digit 2 Digit 3 Digit 4 PRESSURE CONTROL mode POSITION CONTROL mode Valve closed Valve open Closed / open interlock (Valve closed / open by digital input) 0…100 HOLD (position frozen) = valve position (%, 0 = closed / 100 = open) activated ZERO running...
  • Page 69: Service Indication

    1) Provide that battery pack of the VAT controller is charged. Charging time after power up is 2 minutes max.. All parameters are stored in a power fail save memory. 605451EC...
  • Page 70: Operation Under Increased Temperature

    OPERATION Series 651 Operation under increased temperature CAUTION Hot valve Heated valve may result in minor or moderate injury. Do not touch valve and heating device during operation. Once heating is switched off (valve and system) await until the valve is cooled down complete before doing any work.
  • Page 71: Trouble Shooting

    COMPRESSED AIR FAILURE at - Wrong connection of - Connect compressed air in accordance chapter Exhaust «AIRx» compressed air input and installation. output - No compressed air at output - Contact your local VAT service center for support. exhaust 605451EC Edition 2014-07-10 71/99...
  • Page 72 TROUBLE SHOOTING Series 651 Failure Check Action Pressure reading is wrong - Sensor(s) connected? - Refer to «Electrical connection». - 2 sensor version present at - Check valve version on page 1. Verify configuration. pressure reading is negative valve controller? Refer to «Setup procedure».
  • Page 73: Maintenance

    Before carrying out any maintenance, please contact VAT. It has to be individually decided whether the maintenance can be performed by the customer or has to be carried out by VAT. Please write down the fabrication number of the valve before contact VAT. Refer to chapter «Identification of product»...
  • Page 74: Maintenance Procedures

    In this case grease will separate to PTFE and oil. The oil may flow and contaminate the valve parts. VAT can give the following recommendations for preventive maintenance: heated ≤ ≤ ≤ ≤ 80 °C...
  • Page 75: Replacement Of Isolation Seals And Cleaning

    • O-ring removal tool (see chapter: Accessories) Isopropyl alcohol • VAT cleaning tool (see chapter: Accessories) Electrical power and compressed air is required to perform steps 2 to 9 during disassembly respectively 9 to 2 during assembly. Description Required tool Vent both valve chambers.
  • Page 76 • Isopropyl alcohol 12. Clean out valve body with alcohol. • Use VAT cleaning tool or an Clean room wiper appropriate non metal tool with a cloth to enter valve body. Do not enter valve body with hands! 13.
  • Page 77 Series 651 MAINTENANCE Description Required tool Apply grease deposit Vacuum grease on this side • VAT cleaning tool 17. Clean the valve body. • Isopropyl alcohol 18. Reassembly the valve in reverse order, step 9…3. • Isopropyl alcohol 19. Clean the valve sealing surface.
  • Page 78: Replacement Of Actuator Shaft Seals

    Series 651 7.2.2 Replacement of actuator shaft seals 7.2.2.1 Required tools • • Allen Wrench 2 mm VAT cleaning tool (see chapter: Accessories) • • Allen Wrench 4 mm Vacuum grease (see chapter: Spare parts) • • Allen Wrench 5 mm Clean room wiper •...
  • Page 79 Series 651 MAINTENANCE Description Required tool 6. With one hand press the [Maintenance button] to lower the sealing ring, with your second hand unlock unlock the sealing ring by pressing the handle. 7. Release [Maintenance button]. lock 8. Remove sealing ring. 9.
  • Page 80 MAINTENANCE Series 651 Description Required tool 15. Unfasten all 3 actuator screws and Allen wrench 5 mm remove actuator. 16. Remove actuator shaft seals carefully O-ring removal tool with soft tool. • 17. Clean the actuator feed through and Clean room wiper •...
  • Page 81 Series 651 MAINTENANCE Description Required tool 23. Remove fixation kit and mounting screw for pendulum plate. 24. Clean screw and slightly lubricate Vacuum grease thread. Then reinstall fixation kit. 25. Clean actuator shaft and lubricate it with 0.1 ml vacuum grease. 26.
  • Page 82 MAINTENANCE Series 651 Description Required tool Distance D[mm] between bonnet flange surface and pendulum If actuator was replaced, plate. proceed with step 32, otherwise go to step 34. 45.0 ±0.5 30. Close valve and check if pendulum plate is in center of flange. Check can be done either visual or by measurement.
  • Page 83: Replacement Of Option Board

    Series 651 MAINTENANCE 7.2.3 Replacement of Option board NOTICE Electrostatic discharge Electronic components could be damage. All work on the control and actuating unit has to be done under ESD protected environment to prevent electronic components from damage. NOTICE Burned connector pins (spark) Connector pins or electronic parts could damage, if plugged and unplugged under power.
  • Page 84 MAINTENANCE Series 651 7.2.3.1 Durability of power fail battery The curves in the graph show the estimated life of Ultra Cap PFO in the worst condition (max. sensor load = 1 A, valve heating temperature = 150 °C). If the SPS is not fully loaded (< 1 A) or heating temperature of valve body is lower than 150 °C, the corresponding life time curve will be somewhere in between the upper and the lower curve.
  • Page 85: Retrofit / Replacement Procedure

    Series 651 MAINTENANCE 7.2.4 Retrofit / replacement procedure Top view on control and actuating unit with panel removed: Master board Interface board Option board All boards have a fixed position into control and actuating unit. It is not possible to fit a board in other position as shown in picture above! Do not try out other positions, which maybe destroy the socket of boards! 605451EC...
  • Page 86 MAINTENANCE Series 651 7.2.4.1 Required tools • Pozidriv screw driver size 1 • Open end wrench 4.5mm Description Required tool Remove female screw locks from Open end wrench POWER, SENSOR and INTERFACE 4.5 mm connectors. Pozidriv screw driver Remove the panel screws. size 1 Lift the panel carefully.
  • Page 87 Series 651 MAINTENANCE Description Required tool Remove or replace interface board. Remove or replace master board. Remove or replace option board. Insert master board and interface board in reverse order as disassembled at correct positions (see steps 7 to 6). 10.
  • Page 88: Repairs

    Series 651 Repairs Repairs may only be carried out by the VAT service staff. In exceptional cases, the customer is allowed to carry out the repairs, but only with the prior consent of VAT. Please contact one of our service centers. You will find the addresses on our website www.vatvalve.com.
  • Page 89: Dismounting And Storage

    Series 651 DISMOUNTING AND STORAGE Dismounting and Storage WARNING Unqualified personnel Inappropriate handling may cause serious injury or property damage. Only qualified personnel are allowed to carry out the described work. Dismounting NOTICE Contamination Gate and other parts of the valve must be protected from contamination. Always wear clean room gloves when handling the valve.
  • Page 90: Storage

    DISMOUNTING AND STORAGE Series 651 Storage NOTICE Wrong storage Inappropriate temperatures and humidity may cause damage to the product. Valve must be stored at: – relative humidity between 10% and 70% – temperature between +10 °C and +50 °C – non-condensing environment NOTICE Inappropriate packaging Product may get damaged if inappropriate packaging material is used.
  • Page 91: Packaging And Transport

    If products are radioactively contaminated, the VAT form «Contamination and Radiation Report» must be filled out. Please contact VAT in advance. • If products are sent to VAT in contaminated condition, VAT will carry out the decontaminating procedure at the customer's expense. 10.1...
  • Page 92: Transport

    10.2 Transport NOTICE Inappropriate packaging Product may get damaged if inappropriate packaging material is used. Always use the original packaging material and handle product with care. VAT disclaims any liability for damages resulting from inappropriate packaging. 92/99 Edition 2014-07-10 605451EC...
  • Page 93: Disposal

    Series 651 DISPOSAL Disposal WARNING Unqualified personnel Inappropriate handling may cause serious injury or property damage. Only qualified personnel are allowed to carry out the described work. 605451EC Edition 2014-07-10 93/99...
  • Page 94: Spare Parts

    «Identification of product». This is to ensure that the appropriate spare parts are supplied. • VAT makes a difference between spare parts that may be replaced by the customer and those that need to be replaced by the VAT service staff. •...
  • Page 95: 12.1.1 Valve Unit With Seals And Grease

    346960 346960 322336 B2 *) 346971 346971 346963 *) Refer to figures on next page to check for actuator position options. Use only spare parts manufactured by VAT to assure safe and reliable operation All “ 605451EC Edition 2014-07-10 95/99...
  • Page 96: Control And Actuating Unit

    All sizes Product ordering number 650 . . - ..Too many to list. Please contact Control and actuating unit VAT. Option board with SPS module 371399 (±15 VDC sensor power supply) Option board with PFO module...
  • Page 97: Accessories

    • DB-25 male INTERFACE plug Service Box 2 601BS-29NN-000 Control panel (rack-mount version of 602BS-29LE-000 Service Box 2) O-ring removal tool 234859 VAT valve cleaning tool 305709 12.1.3.1 Centering ring with Viton o-ring Description Valve size DN 160 / 6” DN 200 / 8”...
  • Page 98: Appendix

    APPENDIX Series 651 Appendix No information entered on time. 98/99 Edition 2014-07-10 605451EC...
  • Page 99 Series 651 This page left blank intentionally. 605451EC Edition 2014-07-10 99/99...

Table of Contents