VAT 650 Series Installation, Operating, & Maintenance Instructions page 70

Pendulum control & isolation valve with cc-link interface with valve cluster functionality
Table of Contents

Advertisement

CLUSTER VALVE STATUS bitmap table:
This bitmap corresponds to the CLUSTER VALVE MONITORING ADDRESS.
Bit
0-1
ACCESS MODE
2
FREEZE MODE
3
OFFLINE STATUS
NOT USED (reserved)
4-7
8
SERVICE REQUEST
9
COMPRESSED AIR
POWER FAILURE
10
BATTERY
NOT USED (reserved)
11-15
CLUSTER VALVE WARNINGS bitmap table:
Bit
OUT OF RANGE:
CLUSTER VALVE
0
FREEZE POSITION
SETPOINT
OUT OF RANGE:
CLUSTER VALVE
1
FREEZE ADDRESS
SETPOINT
OUT OF RANGE:
2
CLUSTER VALVE
CONTROL SETPOINT
OUT OF RANGE:
CLUSTER VALVE
3
MONITORING ADDRESS
SETPOINT
NOT USED (reserved)
4-7
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4" - 10"), CC-Link
bit 1
bit 0
= LOCAL
0
0
= REMOTE
0
1
1
0
= LOCKED
Valve is in freeze mode (the slave valve is separated from the cluster)
No communication with cluster valve
-
Valve movement tight
Compressed air pressure < 4 bar (only for valves with compressed air)
Not ready, voltage too low
-
Value of CLUSTER VALVE FREEZE POSITION SETPOINT is out of range
Value of CLUSTER VALVE FREEZE ADDRESS SETPOINT is out of range
Value of CLUSTER VALVE CONTROL SETPOINT is out of range
Value of CLUSTER VALVE MONITORING ADDRESS SETPOINT is out of range
-
Description
Description
280672EB
2010-12-15
70/94