VAT 650 Series Installation, Operating, & Maintenance Instructions page 43

Pendulum control & isolation valve with cc-link interface with valve cluster functionality
Table of Contents

Advertisement

4.
Data type of pressure and position values (optional)
The «data type of pressure and position» can be configured by 'Control View', 'Control Performance Analyzer', 'Universal
Hyper Terminal' or 'Service Box 2'.
The «set-command» is: «s:23xxy00000». The xxy value is the data type of a pressure and position signal.
y: 0 = signed integer(32 bit), 1 = floating point (32 bit, IEEE-754 standard), default = 0
xx: signal number in the buffer
xx
Value
00
Pressure
01
Pressure sensor 1
02
Pressure sensor 2 (optional, only in case of 2 sensor version)
03
Position
04
Not used – reserved
05
Cluster valve position
06
Pressure setpoint
07
Position setpoint
08
Not used – reserved
09
Not used – reserved
10
Not used – reserved
11
Cluster valve freeze position setpoint
The «get-command» is: «i:23xx». The answer returns the data type of a pressure and position signal
The y value is the current data type of buffer value xx.
Example «get-command» with Terminal: Get the data Type of Position setpoint:
Note: If at start up the data type value in the memory is out of range the default value is taken. In this case the data type is
set to default value (0 = singed integer) and the get command i:23 add a string "False":
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
Installation, Operating & Maintenance Instructions
Series 650 DN 100-250 (I.D. 4" - 10"), CC-Link
«i:23xxy00000».
280672EB
43/94
2010-12-15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents