Inserting FortiGate-5000 and FortiSwitch-5000 modules into a FortiGate-5050 chassis

Inserting FortiGate-5000 and FortiSwitch-5000 modules into a
FortiGate-5050 chassis
38
1
Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal
surface on the chassis or frame.
2
Loosen the screws and remove the protection plate.
3
Insert the black -48V and red RTN wires through the power wire fixture (see
Figure
23).
4
Connect the black -48V power wire from the FortiGate-5053 power converter tray
V- terminal (the right connector) to the terminal on the FortiGate-5050 power input
connector labelled (-DC in).
5
Connect the red RTN return wire from the FortiGate-5053 power converter tray
unmarked connector (the left connector) to the terminal on the FortiGate-5050
power input connector labelled RTN.
6
Make sure the power wires are secured to the chassis using the power wire fixture
and tie wraps if required.
7
Optionally label the black wires -48V.
8
Optionally label the red wires RTN.
9
Re-attach the protection plate.
10
Connect the FortiGate-5053 power converter tray to AC power.
To connect the FortiGate-5050 chassis to Data Center ground
The FortiGate-5053 power converter tray does not have a ground connector. So,
even if you are using a FortiGate-5053 power converter tray to supply DC power
to your FortiGate-5050, you must use the procedure
5050 chassis to Data Center ground" on page 31
Data Center ground.
You can insert FortiGate-5000 series and FortiSwitch-5003 modules into the
FortiGate-5050 chassis. Arrange the modules in slots as required for your
configuration. FortiGate-5000 series modules can be installed in any
FortiGate-5050 slots. FortiSwitch-5003 modules can only be installed in slots 1
and 2.
Caution: FortiGate-5000 series and FortiSwitch-5000 series modules must be protected
from static discharge and physical shock. Only handle or work with FortiGate-5000 series
and FortiSwitch-5000 series modules at a static-free workstation. Always wear a grounded
electrostatic discharge (ESD) preventive wrist or ankle strap when handling FortiGate-5000
series or FortiSwitch-5000 series modules.
Caution: Do not operate the FortiGate-5050 chassis with open slots on the front panel. For
optimum cooling performance and safety, the slots must contain a FortiGate-5000 series
module or a cover and the removable power supply panel must be installed.