Enterasys Matrix 7G4282-41 Hardware Installation Manual page 33

Dfe-platinum series
Hide thumbs Also See for Matrix 7G4282-41:
Table of Contents

Advertisement

Example 4
(Figure
Shows chassis slots 1 through 5 populated with a mix of 6x1xx, 6x2xx, and 6x3xx modules 
and only third generation modules in slots 6 and 7.
In this module arrangement, the 6x3xx module provides a proxy bridge, which enables 
the 6x1xx and 6x2xx modules to communicate with 6x3xx modules in slot 6 or 7. If more 
than one 6x3xx module is installed in slots 1 to 5, the module in the lowest numbered slot 
performs the proxy function for slots 6 and 7. Therefore, if a 6x3xx module is already 
performing the proxy function, and another 6x3xx module is inserted into a lower 
numbered slot, connectivity will be temporarily interrupted, as the new board takes over 
the proxy function. When a 6x3xx module in a lower numbered slot is removed, and there 
is a 6x3xx module in a higher numbered slot, communication is not interrupted.
For Local Management, plugging the Local Management connection into the 6x3xx 
modules will allow management connections to all 6x1xx, 6x2xx, and 6x3xx modules. If 
the Local Management connection is to a 6x1xx or 6x2xx board, only the modules in the 
first five slots will be recognized by the management client.
Rule: There must be at least one 6x3xx module in slots 1 through 5 to enable 
communications between the 6x1xx, 6x2xx, and 6x3xx modules.
Example 5
(Figure
Shows chassis slots 1 and 5 populated with 6x1xx, 6x2xx modules, respectively; slots 2 
through 4 with DFE‐Platinum modules without a bridging module; and slots 6 and 7 with 
6x3xx modules. 
In this module arrangement, the 6x1xx and 6x2xx modules in slots 1 and 5 can only 
communicate with each other, because there is no 6x3xx module in one of the first five 
slots to serve as the proxy bridge to communicate with the 6x3xx modules in slots 6 and 7. 
The 7x4xxx DFE‐Platinum modules in slots 2, 3, and 4 will operate under one IP address. 
Since there is no bridging module (7H4382‐25, 7H4382‐49, 7H4383‐49, or 7H4385‐49), the 
DFE‐Platinum modules will not communicate with any other modules in the chassis.
Rule: In this example, there must be at least one 6x3xx series module, and a bridging 
module (7H4382‐25, 7H4382‐49, 7H4383‐49, or 7H4385‐49) in slots 1 through 5 to enable 
communications between all generations of modules in the chassis.
Example 6
(Figure
The module arrangement in this example is similar to the one shown in Figure
described in Example 5. The only difference is that a bridging module is installed in slot 2, 
enabling all modules to communicate with each other.
Rule: In this example, the 7H4382‐25 serves as both the FTM1‐to‐FTM2 bridge and the 
five‐to‐seven slot proxy bridge. The 6x3xx does not serve as a proxy bridge in this 
configuration because the 7H4382‐25 is in a slot with a lower number. You can use the 
7H4382‐25, 7H4382‐49, 7H4383‐49, or 7H4385‐49 as a bridging module depending on the 
need.
3-2,
D)
3-2, E)
3-2, F)
Enterasys Matrix DFE-Platinum Series Hardware Installation Guide
Backplane Connections and Installation Rules
3‐2, E and
3-5