Commissioning
Preparing the device address setting via the PROFIBUS
If you set the rotary switches to a value between "7Eh" and "FEh", the device is
allocated the address "7Eh" (126), which you can modify during operation via the
PROFIBUS. The new address is stored in the volatile memory.
If you set the rotary switches to "FFh", the factory preset address 126 is selected.
You can modify the address during operation via the PROFIBUS interface. The
new address is stored in the non-volatile memory, which means the modified
address becomes valid when the device is switched off and back on again.
1. Set the rotary switches to "7Eh" ... "FEh" or "FFh".
2. Switch the device off and back on again so that the PROFIBUS adopts the
device address.
Setting the device address via the PROFIBUS
The device supports the PROFIBUS service "Set_Slave_Add" via the Service
Access Point SAP55 of a DP slave. You will require a DPM2 master here.
You must set the address using a suitable projecting tool (e.g. Siemens "STEP7 /
SIEMATIC Manager" or VAZ-PB-SIM "PROFIBUS DP Master Simulator").
Setting the device address using the Siemens "STEP7 / SIMATIC
Manager"
1. To assign the PROFIBUS interface parameterization to the "S7ONLINE" ac-
cess point, select "Options", "Set PG/PC interface ..." and "PC adapter
(PROFIBUS)" from the SIMATIC Manager menu.
2. To allocate the address, select "Target system", "PROFIBUS" and "Allocate
PROFIBUS address ..." from the HW Config menu and enter or select the
PROFIBUS address. Press "OK" to change the address.
Setting the device address using the VAZ-PB-SIM "PROFIBUS DP
Master Simulator"
1. Select "Address" and "Modify address of PROFIBUS slave ..." from the menu.
2. Enter the old and new address.
3. Press "OK" to change the address.
25