Installation
You must establish a low resistance and low inductance connection between the
shields and ground so that the shielding is not interrupted through the metal
enclosure. The complete electronics system and all routed cables are therefore
located within a Faraday cage.
5.3
Mounting
If you would like to the mount the IDENTControl Compact to a DIN mounting rail,
we recommend using mounting aid ICZ-MH05-SACB-8.
Note!
The rotary switches used to select the device address are located on the
underside of the IDENTControl Compact. These rotary switches are no longer
accessible once the IDENTControl Compact is installed.
Set the rotary switches before mounting the IDENTControl Compact ().
5.4
Device connection
Electrical connection using plug connectors makes installation simple.
5.4.1
Power Supply
Connect the power supply using an M12 connector. A plug with the following pin
assignment is located on the enclosure:
1
1
2
3
4
Compatible connecting cable see chapter 4.2.2.
5.4.2
R/W head
You can connect either an inductive R/W head (125 kHz or 13.56 MHz) or an
inductive R/W head with electromagnetic coupling (UHF with 868 MHz) to the
IDENTControl Compact.
socket at housing
3
Compatible R/W head see chapter 4.1.1.
16
4
3
2
+ 24 V
NC
GND
NC
4
1
2
3
1
4
5
5
2
read/write head
+
A
-
B