ID61/62 Series Panel - Installation, Commissioning & Configuration Manual

2.8 RS232 Interface Connections

The panel is fitted with a standard 9-way 'D'-type RS232
Interface connector, located at the bottom left-hand
corner of the PCB assembly. The RS232 connector is
used for the following purposes:
a. Configuration using the PC Support Tool (refer to
997-405, ID61/62 Series Panel - Offline
Configuration Manual).
b. Upgrading the Panel Software (refer to 997-415, ID61/
ID62 Series Panel - Upgrading Instructions).
Before starting any of the above operations ensure
suitable anti-static precautions have been taken.
The RS232 connector has the following pin out:
Pin
1
Data Carrier Detect (DCD)
2
Receive (RX) Data
3
Transmit (TX) Data
4
Data Terminal Ready (DTR)
5
GND
6
Data Set Ready (DSR)
7
Request To Send (RTS)
8
Clear To Send (CTS)
9
Not Applicable
Note: Pin numbers marked thus '*' are the only
required connections. Any others fitted will
be ignored.
A Data Transfer Lead (PN: 082-173) is required. Jumpers
must be removed as follows:
1 Remove the cover [refer to Section 2.5.1, Removing
the Cover(s)] to access the panel electronics.
2 Remove the Jumper Links JP6, E_FLT (earth fault
monitoring) and JP7, MEM (configuration lock).
Note: Refer to Section 4.3.1 Jumper Link Options/
Earth Fault Monitoring (JP6) when connecting
third-party equipment to the panel.
3 Fit the Data Transfer Lead to the RS232 Interface
socket connector, SK3.
4 Perform required operation.
5 After satisfactory completion disconnect the lead and
then fit the jumpers.
17
Description
997-457-000-8, Issue 8
January 2010
*
*
*
*
*