Non-VIEW
Sensor Sensitivities
TM
The ID61/62 panel supports co-operative multi-sensing
for sensor types other than VIEW
ION, OPT, MLT, OPX/SM2, SM3 or SM4 sensors a third
menu option, Group, is displayed with the default group
number displayed in the brackets. A sensor may be
assigned to one of up to 50 groups and mixed with other
sensor types. Allocation to a non-zero group enables a
sensor's inclusion in the AWACS
allocation of a sensor to Group 0 excludes it from the
AWACS
TM
algorithm and the existing alarm detection
algorithm is used instead (the sensor will operate as a
stand-alone device).
Note: When transferring a configuration from an earlier
version panel, the group number is defaulted to
'1'. This must be changed to '0' for all devices not
being monitored by the AWACS
VIEW
devices learnt using software version 5.00,
TM
or above, will default the group to '0'.
Alarm and pre-alarm sensitivity levels can be set in
addition to selecting a multi-sensing group.
1 To change the group, press the '
numeric keypad.
[Sensor nn - AAA]
1 : Alarm (L5,5)
2 : Day (L5,5)
2 Enter a new group number, e.g. 2, and press '
confirm.
[Sensor nn - AAA]
Enter new AWACS Group : ____
3 Using the numeric keypad, to change the alarm and/
or pre-alarm sensitivity levels press the
or to change the Day Mode sensitivity setting, press
the
pushbutton.
2
[Sensor nn - AAA]
1 : Alarm (L5,5)
2 : Day (L5,5)
4 At the appropriate prompt enter the desired sensitivity
setting.
A2 - 2
. When configuring
TM
algorithm. However,
TM
TM
algorithm.Non-
' button on the
3
Sensitivity
3 : Group (0)
Sensitivity
< : Cancel
pushbutton
1
Sensitivity
3 : Group (2)
' to
5