Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 107

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
VIEW
sensors remain
TM
inoperable for 60 seconds
after being replaced
while calibrating.
VIEW
Co-operative Multi-sensing
TM
Co-operative sensing is carried out automatically between
VIEW
sensors in the same group and across sensor
TM
type. Grouped sensors co-operate within the group
providing greater levels of sensitivity with a reduced risk
of false alarms. When first installed, VIEW sensors are
all allocated to group 1 but they can be configured up to
50 groups. Sensors allocated to group '0' operate
independently. An example of VIEW
operative grouping is given below:
Address Type
03
AVS
04
AVS
05
AVS
09
AVR
10
AVS
11
AVS
15
AVS
16
AVS
17
AVS
27
AVS
Each group can have one or more VIEW
configured as reference sensors (AVR). Sensors placed
such that external smoke influences (eg. bonfires and
exhaust fumes) can be detected early should be
configured as AVRs. When these influences are detected
by the AVR the group can then be temporarily desensitized.
VIEW
Sensor Sensitivity
TM
Most local codes of practice require very low levels of alarm
sensitivity selection be tested on-site before implementation.
Alarm sensitivity level 6 (L6) and below generally require
a 90-day test to ensure the sensor environment is suitable
for a higher sensitivity setting. This is not required for
high levels of pre-alarm sensitivity selection.
Dynamic Intelligent Grouping (DIG) Operation
The Dynamic Intelligent Grouping (DIG) Operation only
performs calculations on up to five sensors with the highest
value. This is an advantage in a group of many sensors, as
any condition will quickly be recognised by the panel.
A2.1 Calibrating VIEW
Each VIEW
sensor is automatically calibrated on first
TM
operation with the panel. This calibration is completed at
one of the following times:
a. Approximately 90 secs after the panel is powered on.
b. 60 secs after the sensor is installed on a panel which
is already operating normally.
During this initial period (which is required to allow the
VIEW
sensor to stabilise) the sensor must not be
TM
exposed to smoke or other abnormal conditions,
otherwise the panel may report a sensor fault.
If a VIEW
sensor is removed from the operational loop,
TM
or communication with the panel is broken for a minimum
of 30 secs, recalibration will take place automatically.
Note: If a VIEW
TM
replaced with a new one, wait at least 30 secs after
removal before replacing it.
A2 - 3
sensor co-
TM
Zone
Group
1
01
1
02
1
02
1
01
1
02
1
00
2
01
2
01
2
02
2
01
TM
Sensors
TM
sensor is removed and cleaned, or
997-457-000-8, Issue 8
January 2010