Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 82

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
EN 54-2 : 7.7.1
One output on the panel
must be configured as a
fire output. This may be
an unmonitored relay
output.
1
Use the '
2
to change the output
circuit being configured
2
997-457-000-8, Issue 8
January 2010
5.6.3.1 Output Type Setting
This option allows the configuration of the panel's on-
board output circuits. To change the configuration:
1 Press the '
[ON-BOARD]
1 : Type
Note: The options are Monitored Output Circuit Sounder
2 To select the new type, using the numeric keypad
[ON-BOARD]
>SDR<RLY CTL TxD RLE CTE EST ESO ESE S
/
' buttons
8
Note: Only those types valid for the chosen output are
5.6.3.2 CBE Rule Setting
This option allows each of the panel's on-board output circuits
[ON-BOARD]
1 : Type
1 Using the numeric keypad press the '
[BO n] CBE Rules
1 : Base [01 : No]
2 You are now prompted to enter a new CBE Base Rule.
[BOn] CBE Rules
Enter CBE Rule :
78
' button on the numeric keypad. The
1
LCD prompts for the selection of an output type:
B01 (SDR)
2 : CBE Rule (01)
(SDR - default setting), High-load Monitored Output
Circuit Sounder (SDH), Transmission Device (TxD),
Monitored Output Circuit Relay (CTL), Monitored
Output Circuit Relay
(CTE), Unmonitored Output
1
Circuit (RLY), Unmonitored Output Circuit
extinguishing system output types (EST, ESO, ESE).
press the '
', '
' or '
1
2
B01 (SDR)
available. The panel's -VE Outputs (B05/B06) are
unmonitored and are thus fixed as type 'RLY'.
to be assigned to a CBE Rule range. Refer to Section
5.6.1.5 CBE Rules for more details on range setting. To
change the CBE Base Rule, proceed as follows:
B0n (AAA)
2 : CBE Rule (nn)
select the CBE Rule option:
01 - - - - - - - - - - - - --- - - - - - - - 1 6
YYYYYYYYYYYYYYYY
Use the numeric keypad to enter the CBE Rule
required for the output circuit and use the '
to confirm the selection.
01- - - - - - - - - - - - - - - - - - - - - - - 24
_
Refer to Section 5.7, Control-by-Event Output
Rules for information concerning the CBE Rules. The
rule defines whether the output will respond to zonal
alarms and/or the END DELAY / EVACUATE
pushbutton. It also determines whether the output is
silenceable and whether any delays are interruptable.
3: Mon. : RES.
: Change < : Exit
(RLE) and
1
' button as required.
3
3: Mon. : RES.
: Change < : Exit
' button to
2
' button
5
<: Cancel