Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 118

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
EN54-2
Description
Option
INDICATIONS
7.10.4
Fault signal from fire protection equipment
7.13
Alarm counter
8.3
Fault signals from points
8.4
Total loss of power supply
CONTROLS
7.11.1
Delays to outputs
7.11.2
Manual or automatic switching of delays to outputs
7.12.1
Dependency on more than one alarm signal: Type A
7.12.2
Dependency on more than one alarm signal: Type B
7.12.3
Dependency on more than one alarm signal: Type C
9.5
Disablement of each address point
10
Test condition
OUTPUTS
7.8
Fire alarm device(s)
7.9.1
Fire alarm routing equipment
7.9.2
Fire alarm routing equipment with alarm confirmation Required
7.10.1
Automatic fire protection equipment: Type A
7.10.2
Automatic fire protection equipment: Type B
7.10.3
Automatic fire protection equipment: Type C
8.9
Fault warning routing equipment
11
Standardized I/O interface
Interface meets VdS 2540 which requires DIN 14675 & 4662, but not full EN54-2, 11.
1
Appendix 4
EN54-2- Options with Requirements
In addition to satisfying the requirements of EN54-2
Options with Requirements, the table below defines
whether the CIE is configurable in accordance with the
mandatory or optional requirements of VdS 2540.
1
A1
Fault Signal From CIE
This is a VdS 2540 requirement. The CIE provides for
this EN54-2 option.
The CIE comprises a volt-free contact relay configured
as a dedicated fault output. Refer to Section 4.4.5
Configuration Outputs C and D and Section 5.6.3 On-
board Circuits for more details.
A2
Alarm Counter
This is a VdS 2540 requirement. The CIE can record a
maximum number of 9,999 alarm events. If this limit is
reached the alarm counter will automatically reset to zero.
It is not possible to reset the counter through the CIE,
except at access level 4.
A3
Fault Signals from Points
This is an optional VdS 2540 requirement. The CIE will
display fault signals from individual sensors and devices.
A4 - 1
VdS 2540
C.I.E.
Option
Configurable?
Required
Yes
Required
Yes
Optional
Yes
Optional
No
Optional
Yes
Optional
Yes
Optional
No
Required
Yes
Prohibited
No
Optional
Yes
Required
Yes
Required
Yes
Required
Yes
Yes
Optional
Yes
Optional
No
Required
Yes
Required
Yes
Required
Yes
997-457-000-8, Issue 8
January 2010