Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 66

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
5
6
5
5
997-457-000-8, Issue 8
January 2010
5.5.5.4 Primary/Extend Delay Timers
The Primary Delay Timer allows an initial investigation time
of up to 300 seconds (default 30 seconds) to be entered
or changed. The Extend Delay Timer allows an additional
delay (default - 3 minutes) to be entered or changed. The
total delay time cannot exceed 10 minutes. To set delay
times:
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
[S1
Setup]
5: Day / Night Settings
1 From the Setup menu screen, press the '
on the numeric keypad to enter the Day/Night
Settings menu. The Day Mode Activity screen is
displayed first.
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
2 Pess the '
' button. The display then prompts you
6
for the new value:
[Setup]
Primary Delay Time = 30 Seconds
Enter new value ____
3 Enter the required delay time using the numeric
buttons; (e.g. to set the delay time to the maximum
value of 300 seconds, first enter '3', then enter '0', '0').
[Setup]
Primary Delay Time = 30 Seconds
Enter new value 300
4 Press the '
' button to confirm and return to the
5
Setup menu screen.
6 Repeat steps 1 to 5 for the Extend Delay Time, using
the Extend Delay Time display and a maximum value
of 10 minutes.
5.5.5.5 Heat Det. End Delay
The Day Mode function, Delays to outputs, can be
cancelled when a heat sensor goes into alarm. To select
the Heat Det. End Delay option:
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
[S1
Setup]
5: Day / Night Settings
1 From the Setup menu screen, press the '
on the numeric keypad to enter the Day/Night Settings
menu. The Day Mode Activity screen is displayed first.
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
62
: More
4: Peripheral Options
5
: More
< : Exit
: Confirm
< : Cancel
: Confirm
< : Cancel
: More
4: Peripheral Options
5
: More
< : Exit
: More
' button
: More
' button

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id61

Table of Contents