ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Any sensor logging more
than 100 days in a
maintenance condition is
'promoted' to a maintenance
fault. The panel indicates a
general fault condition.
6
A2.5 MULTI, Optiplex and SMART Multi-Sensors
In addition to MULTI and Optiplex/SM2 Multi-sensors the
ID61/62 panels now support SMART 3 (SM3) and SMART
4 (SM4) Multi-Criteria Sensors. All multi-criteria sensors
feature photo, thermal and infra-red (IR) sensing
capabilities. The SMART 4 sensors feature CO gas
detection in addition to photo, thermal and infra-red (IR)
sensing capabilities.
As with ION, OPT, MLT and OPX/SM2 device types SM3
and SM4 sensors can be assigned to multi-sensing
groups, as described earlier in this appendix under Non-
VIEW
Sensor Sensitivity.
TM
To change the alarm and pre-alarm sensitivity thresholds
of the SM4 sensors, refer to the procedure described
earlier in this appendix under Non-VIEW
Sensitivity.
SMART 4 CO Element - Warning of Life Expiry
When the CO detection element of the SMART 4 sensor
approaches the end of its useful life (approximately 6
calendar months before sensor replacement is needed) a
maintenence notification for that sensor is created in the
Maintenance log. This maintenance log entry is intended
as a service engineer advisory that one or more sensors
will need replacing some time in the near future. However,
during this period the SMART 4 sensor will still perform as
it did before it entered the maintenance 'advisory' state.
Maintenace Event Log Access
This maintenence notification event log (access level 3
is required) can be accessed via the View Mode menu
(see the Operating Manual, Section 4.12) as described
below.
To access the maintenance log, first select the View Mode
menu:
[U0 View]
1: Log 2: Devices
4: Input Events
5: Disabled
[U0 View]
6: Maint.
8: Voltages
1 Using the numeric keypad press the '
select the Maintenance option. You will be prompted
for an Access Level 3 passcode as below:
COMMISSION MODE ACCESS
Enter Level 3 passcode
Note: This screen reverts to the View Mode menu after
2 mins if no key has been pressed.
A2 - 7
TM
3: Faults
: More
7: Alarm Count
9: Version
' button to
6
_
<: BackSp
997-457-000-8, Issue 8