ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
-
-
+
+
+
-
+
-
TB5
Apply power
BEFORE making any
RS485 connections.
+
-
+
-
1
2
+
-
+
-
TB4
4 If reversed device(s) are indicated in step 3, they may be
located by successive halving of the loop (if the site layout
makes this difficult, the affected section of the loop can be
identified from the panel fault messages after the system
has been configured and the links in the isolators removed).
Connecting to the Panel
When the Loop wiring has been checked and found to
be satisfactory, do the following:
1 Remove the temporary links on the isolator units.
(OPAL protocol-compatible sensor bases, B501 AP,
automatically link out so these can be ignored at any
addresses where devices with an internal isolator are
installed).
2 Connect the loop wiring to the panel.
When connecting, observe correct polarity! The
ends nominated as + and - must be fitted to the
correct terminals.
3 When the Loop wiring has been connected, apply the
mains supply and then fit the interlink wire to the
batteries.
4 Check the LCD and LEDs for indications of any faults.
If faults exist, correct them and reset the panel.
5 Configure the Loop following the procedures in
Section 5.6.1, Signalling Line Circuit (SLC) -
Devices and/or Section 5.6.2, Signalling Line
Circuit (SLC) - Learn.

4.4.2 RS485 Communications Link

When the Isolated RS485 Board has been installed in
the panel, checked and found to be satisfactory:
1 Connect the RS485 Communications Link as
described in Section 2.7.
When connecting, observe correct polarity! The
ends nominated as B and A must be fitted to the
correct terminals.
2 When the RS485 Communications link has been
connected, apply the mains supply and then fit the
interlink wire to the batteries.

4.4.3 DC Auxiliary Output

BEFORE connecting any circuit to the monitored DC
Auxiliary Output (at either of two connectors), check that:
1 The external wiring is not short circuit.
2 There are no forward-biased diodes (as used for
example with end-of-line, power-monitoring relays)
connected across the external wiring.
When connecting, observe correct polarity! The
ends nominated as + and - must be fitted to the
correct terminals.
25
997-457-000-8, Issue 8
January 2010