Internal Checks; Jumper Link Options - Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
JP6
UNLOCKED
JP7
MEM
JP8
JP7
FLASH PRG
MEM
ENABLE
LOCKED
ENABLED
EN 54-2 : 8.2.4c.
Earth Fault Monitoring
is required.
DO NOT remove link if
there is an existing earth
fault. If link is removed,
ensure it is fitted before
replacing front cover.
JP6
E_FLT
DISABLED

4.3 Internal Checks

When all PCBs have been installed and all cabling has
been successfully checked, the appropriate jumper links
may need to be configured, as described below.

4.3.1 Jumper Link Options

Software Upgrade (JP8)
The Software Upgrade Jumper in conjunction with the
Upgrade kit is used to upgrade the panel operating software.
To enable the panel upgrade, fit a link to JP8 and connect
the appropriate cable. The link JP8 must be removed on
completion of the upgrade (see 997-468, ID51/52 Series
Panel - Upgrading Instructions). JP8 is situated to the
right of the Configuration Jumper at the bottom of the PCB.
Configuration Lock (JP7)
The Configuration Lock Jumper is used to lock and unlock
the system configuration. If the link is fitted the system
configuration is locked and changes will NOT be allowed.
If the link is removed system configuration is possible.
The panel can only be configured with the Configuration
Lock (JP7) in the unlocked position. The jumper is situated
to the right of the RS232 connector at the bottom of the
PCB.
Earth Fault Monitoring (JP6)
Earth fault monitoring should be enabled during normal
DISABLED
operation; this is the default condition and is indicated by a
fitted jumper link on JP6 located between the printer and
JP8
RS232 connectors on the bottom of the PCB. This is clearly
marked on the PCB with 'E_FLT' below the jumper. To
FLASH PRG
disable the earth fault monitoring, remove the link.
ENABLE
The presence of an earth fault is indicated by a yellow
Earth Fault and general Fault LED.
Warning: If an earth fault already exists, DO NOT attempt
Note: Direct connection of a VDU etc. to the RS232 serial
Important Notice
The RS232 serial port (connector SK3) is NOT
isolated. It must only be used to connect suitably-
isolated devices.
JP6
E_FLT
ENABLED
to connect additional equipment likely to cause
earth faults as damage may result, i.e. inhibiting
the monitoring will not protect the equipment.
port D-type socket SK3, will result in an earth fault
and potential damage to the connecting equipment.
This fault can be removed by use of an isolated
RS232 link or by (temporarily) disabling the earth
leakage detection. Wait at least one minute after
disabling the earth fault monitoring circuit before
making a connection at SK3.
23
997-457-000-8, Issue 8
January 2010