ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
CBE Rule:01
>:Change
:Accept
CBE Rule:01
>:Change
6
997-457-000-8, Issue 8
January 2010

5.7.7 Two Zone

The Two Zone option has two states, Yes (Y) and No
(N). This option is available with the Fire, Pre-Alarm and
Plant Warning rules. To change the Two Zone rule setting:
1 Press the '
select the Two Zone option from the menu below.
CBE Rule:01
7
2 Press the '
Refer to Section 5.7, Control-By-Event Output
Rules for further information.
Two Zone = [N]
< : Cancel
:Accept
3 Confirm the selection by pressing the '
5
cancel the selection, press '
menu below is re-displayed.
CBE Rule:01
86
' button (using the numeric keypad) to
7
6:Class Change
7:Two Zone
9:Zones
' button to select the required setting.
6
Two Zone = [Y]
< : Cancel
'. In either case the
4
6:Class Change
7:Two Zone
9:Zones
: More
' button. To
5
: More