Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual page 100

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
+
CH G
R IN
-
H N/
C N/
O CO
M
+
-
TE M
P S
N S
R
b
Total AUX DC power available - split
2
across both AUX and FBF outputs.
Back light off
3
4
Back light on, fire relay and two sounder
relays on.
Panel PSU input range:
DC Auxiliary Rating
Output voltage range:
Maximum load
2
:
Fuse rating:
Cables should be capable of carrying a minimum 1A.
Fuse rating:
a
Fuses:
The location of the panel fuses is given here, together with their
ratings and their type.
a. MF1
Mains Supply
b. FP2
Battery Charger Fuse
T = time delay (i.e. anti-surge), H = high break capacity ceramic,
as defined by EN 60127.
Panel Current:
Unloaded:
Main Board
Quiescent
3
:
Alarm
:
4
Printer (optional)
Quiescent:
Printing:
Isolated RS485 Board (optional)
Maximum:
PSU operating current (when PSU is powered
by batteries):
Fully Loaded:
Quiescent:
Alarm:
Batteries:
Internal batteries:
Note: Battery lifetime depends on the ambient temperature;
refer to the battery manufacturer's technical
specification for guidance. (Refer to 'Panel Ratings -
Fully Loaded' for charger limitations).
Maximum battery ratings:
ID61:
ID62:
A1 - 3
Non-boosted - 19.9 -28.5Vdc
Boosted - 26.0 -28.3Vdc
20 to 28V
0.25A
Cables should be capable of
carrying a minimum 1A.
Not applicable
Not applicable
T 5A H 250V
T 6.3A H 250V
70mA
130mA
11mA
200mA (Average)
25mA (Average)
60mA
2.9A
3A
Two 12V, sealed, lead-acid types
MUST be used.
12Ah
38Ah
997-457-000-8, Issue 8
January 2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id61

Table of Contents