5.5.4.2 Number of Repeaters
The Number of Repeaters menu allows the quantity of
repeaters connected to the RS485 Communications Link
to be entered. The panel displays a fault if this quantity
does not equal the number of repeaters connected. To
enter the number:
1 From the Peripheral Options screen, press the '
[Setup]
> : Change
8
2 Press the '
[Setup]
> : Change
3 Press the '
[Setup]
Enter new value ____
4 Enter the required number using the numeric buttons;
[Setup]
Enter new value 1 0
5 Press the '
5.5.4.3 RS485 Protocol
This option is used to select one of two available protocol
formats when repeaters are connected to the panel via
the RS485 communications link. The options available are:
a. NOTIFIER
b. ARP50/RP50.
The NOTIFIER protocol supports the IDR-2A and IDR-2P
Repeaters.
There are two additional options:
c. BFT/LLT repeater (Sweden only) communications link.
d. DISABLED - disables communication to any device
52
button on the numeric keypad to select the RS485
Communications port option. The RS485 Protocol
setup screen is displayed:
RS485 Protocol =
/
' buttons to step through the
2
8
Peripheral Options until the Number of Repeaters
menu is displayed.
No. of Repeaters = 0
: More
' button to enable the number or
6
repeaters to be entered.
No. of Repeaters = 0
: Confirm
for example if entering a value of 10, first press '1',
then '0'.
No. of Repeaters = 0
: Confirm
' button to confirm the selection or press
5
'
' repeatedly to cancel and return to the Setup menu
4
screen.