Measuring Ranges/Process Value Ranges

The following provides an overview of the measuring value ranges and the
associated process value ranges. The indicated values apply to user scaling that is
not switched on.
The process data is output as signed 16-bit values; the scaling is adjusted to the
measuring area:
Temperature range Pt
Value range
-4000 ... 17000 (-200 ... 850 °C)
Resolution
0.05 °C (K)
Temperature range Ni DIN
Value range
-1200 ... 6000 (-60 ... 300 °C)
Resolution
0.05 °C (K)
Temperature range Ni Tk5000
Value range
-1200 ... 5000 (-60 ... 250 °C)
Resolution
0.05 °C (K)
Temperature range Ni Tk6720
Value range
-1200 ... 5200 (-80 ... 260 °C)
Resolution
0.05 °C (K)
Resistance range 1 k
Value range
0 ... 24000 (0 ... 1200 Ω)
Resolution
0.05 Ω