Rack-mounting a PRI Gateway
1. Slide the PRI Gateway into the rack. Make sure it is supported.
2. Use the four screws to fasten the PRI Gateway to the rack.
3. Ground the PRI Gateway. See

Ground a PRI Gateway

Perform the steps in
Warning:
Only a qualified person must make the connection in the AC electrical panel.
Grounding PRI Gateway components
1. Disconnect the AC power cord from the power outlet.
2. Install a #6 - #10 AWG ground wire from the ground lug at the back of the PRI
3. Place a tag marked DO NOT DISCONNECT on the ground wire at the electrical
54
Media Gateway 1000E PRI Gateway Installation and Commissioning
page 54.
Grounding PRI Gateway components
Gateway to the ground bar/frame ground bar.
panel.
Comments? infodev@avaya.com
Grounding PRI Gateway components
on page 54.