• earthquake areas –additional security measures are required here;
• sites that are higher than 3000 meters above the sea level;
• sites with explosive atmosphere;
• sites with direct sunlight;
• sites with extreme change of ambient temperature;
• wet rooms;
• sites with highly flammable materials or gases; or
• sites with a potentially explosive atmosphere;
2.1.2

Restricted Locations

Where the SMILE-T10 is located on or within 300mm of the wall or structure
separating it from the habitable room, the barrier shall extend —
(i)
1000 mm beyond the vertical sides of the SMILE-T10;
(ii)
300 mm above the SMILE-T10; and
(iii)
to the extent of the bottom of the SMILE-T10.
Please refer to Figure 12.
Figure 12 Distancelimit of Installation to Neighboring Objects
Where the top of the SMILE-T10 is within 300 mm of the ceiling or structure above
the SMILE-T10, the ceiling or structure surface shall be suitably non-combustible for
an area of 600 mm past the extremities of the SMILE-T10.