wet rooms;
sites with highly flammable materials or gases; or
sites with a potentially explosive atmosphere;
2.1.2
Restricted Locations
The SMILE5 shall not be installed —
(a)
in restricted locations, as defined for switchboards in AS/NZS 3000;
(b)
within 600 mm of any hot source, such as water unit, gas heater, air conditioning
unit or any other appliance.
(c)
within 600 mm of any exit;
(d)
within 600 mm of any window or ventilation opening;
(e)
within 900 mm of access to 240 Vac connections; and
(f)
within 600 mm of side of other equipment.
A SMILE5 installed in any corridor, hallway, lobby or the like leading to a fire exit shall
ensure sufficient clearance from the SMILE5 for safe egress and no less than 1 m.
A SMILE5 is considered a source of ignition and therefore shall not be installed within
hazardous area for gas cylinders containing heavier than air gasses and gas relief vent
terminal as defined in AS/NZS 3000.
2.1.3
Barrier to habitable rooms
To protect against the spread of fire to habitable rooms, where the SMILE5 is mounted
on, placed against a surface of a wall or structure that has a habitable room on the
other side, the wall or structure shall be a suitably non-combustible barrier. If the
mounting surface itself is not made of a suitably non-combustible material, a non-
combustible barrier may be placed between the SMILE5 and the surface of a wall or
structure.
Where the SMILE5 is located on or within 300mm of the wall or structure separating it
from the habitable room, the barrier shall extend —
(i)
600 mm beyond the vertical sides of the SMILE5;
(ii)
1200 mm above the SMILE5; and
(iii)
to the extent of the bottom of the SMILE5.
Please refer to Figure 7.