Restricted Locations - Alpha ESS Storion-SMILE-T10 Installation Manual

Energy storage system
Hide thumbs Also See for Storion-SMILE-T10:
Table of Contents

Advertisement

 sites with a potentially explosive atmosphere;
2.1.2

Restricted Locations

Where the SMILE-T10 is located on or within 300mm of the wall or structure separating
it from the habitable room, the barrier shall extend —
(i)
1000 mm beyond the vertical sides of the SMILE-T10;
(ii)
300 mm above the SMILE-T10; and
(iii)
to the extent of the bottom of the SMILE-T10.
Please refer to Figure 9.
Figure 9 Distancelimit of Installation to Neighboring Objects
Where the top of the SMILE-T10 is within 300 mm of the ceiling or structure above the
SMILE-T10, the ceiling or structure surface shall be suitably non-combustible for an
area of 600 mm past the extremities of the SMILE-T10.
Where more than 4 batteries are installed, some batteries shall be installed beside,
distance between two rows batteries shall be not less than 100 mm
SMILE-T10 shall be mounted with the highest point no greater than 2.2 m above the
floor or platform.
___________________________________________________________________
Installation
Alpha ESS Co., Ltd.
Your Smart Energy
Page 15 of 46

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents