“Ee” Drive Memory Chip Error; “C4” Odu Jumper Cap Error - Gree U-Match 5 Series Manual

Table of Contents

Advertisement

GREE
3.4.37 "ee" Drive Memory Chip Error
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display ee
Error judgment condition and method:
If power is connected but the drive board with memory chip cannot detect the memory chip or read the
memory chip data correctly, then it can be judged that drive memory chip error exists.
Possible reason:
■The drive board that needs memory chip is not installed with the memory chip.
■The lead or connector of memory chip is badly welded or short-circuited.
Troubleshooting:
3.4.38 "c4" ODU Jumper Cap Error
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display c4
Error judgment condition and method:
If jumper cap model doesn't match with mainboard, report the error
Possible reason:
■Jumper cap is not installed
■Jumper cap model is wrong
■Detecting circuit is abnormal
ee Drive memory chip error
Drive board is installed with
memory chip or not?
YES
Replace the drive
board .
U-Match 5 SERIES UNIT SERVICE MANUAL
NO
Install the
memory chip .
87

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents