“F0” Indoor Ambient Temperature Sensor Error; “F1” Evaporator Temperature Sensor Error - Gree U-Match 5 Series Manual

Table of Contents

Advertisement

GREE
3.4.8 "F0" Indoor Ambient Temperature Sensor Error
Error display: IDU wired controller and IDU receiver light board will display F0
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
Possible reason:
■Poor contact between ambient temperature sensor and terminal in mainboard interface
■Ambient temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
3.4.9 "F1" Evaporator Temperature Sensor Error
Error display: IDU wired controller and IDU receiver light board will display F1
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
U-Match 5 SERIES UNIT SERVICE MANUAL
64

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents