Troubleshooting:
Note: Please refer to Appendix 1 for the relation between temperature and resistance of temperature sensor.
3.4.13 "F5" Wired Controller Temperature Sensor Error
Error display: IDU wired controller and IDU receiver light board will display F5
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge the
range of AD value, If the sampling AD value exceeds upper limit and lower limit in 5 seconds continuously, report
the error.
Possible reason:
■Poor contact between temperature sensor and terminal in mainboard interface
■Temperature sensor is abnormal
■Detecting circuit is abnormal
Troubleshooting:
Malfunction of
discharge
temperature
sensor
Check if the
discharge temperature sensor on
mainboard is inserted on the
needle stand correctly
Yes
Disconnect
the temperature sensor and
measure if its resistance is
normal
Yes
Replace the
outdoor
mainboard
U-Match 5 SERIES UNIT SERVICE MANUAL
No
on the needle stand
No
Malfunction of
wired controller
temperature
sensor
Replace the
wired controller
68
Correctly insert the
temperature sensor
Replace the
temperature sensor