7 Table of Error Codes for Indoor Unit

Error
Content
Code
L0
Indoor Unit Error
L1
Indoor Fan Protection
L2
E-heater Protection
L3
Water Full Protection
Wired Controller Power
L4
Supply Error
L5
Anti-Frosting Protection
No Master Indoor Unit
L7
Error
Power Insufficiency
L8
Protection
L9
Quantity Of Group Control Indoor Units Setting Error

8 Troubleshooting

The air conditioner is not expected to be serviced by users. Incorrect repair may cause electric
shock or fire, so please contact an authorized service center for professional service. The following
checks prior to contact may save your time and money.
Phenomenon
The unit can't start
The unit stops after running
for a while
Poor cooling effect
Poor heating effect
Indoor fan doesn't start
up during heating
Notes:
If air conditioner still fails to work normally after checking and handling as described above,
please stop using it immediately and contact local service center for assistance.
Multi Variable Air Conditioners Duct Type Indoor Unit
Error
Content
Code
Indoor Units Incompatibility
LA
Error
LH
Low Air Quanlity Warning
Outdoor-Indoor Incompatibility
LC
Error
d1
Indoor Unit PC-Board Error
Ambient Temperature Sensor
d3
Error
Inlet Pipe Temperature Sensor
d4
Error
Outlet Pipe Temperature
d6
Sensor Error
d7
Humidity Sensor Error
Power supply is not connected.
Circuit breaker tripping caused by leakage of electricity.
Input voltage is too low.
Defect of main PC-board.
The inlet or outlet of ODU or IDU are blocked by obstacle.
The filter is dirty.
Too heavy heat load of room(e.g. too many people)
Door or windows is open.
Inlet and outlet of IDU are blocked.
Setting temperature is too high.
Refrigerant is insufficient (e.g. refrigerant leakage)
The filter is dirty.
Door or window is open.
Setting temperature is too low.
Refrigerant is insufficient (e.g. refrigerant leakage)
At starting, the IDU fan could not operate till the heat exchange become
hot, for preventing delivering the cool air.
At defrosting, the IDU fan stopped due to system switch to cooling
mode. for preventing delivering the cool air, and resume operating after
defrosting.
19
Error
Code
Water Temperature Sensor
d8
Error
d9
Jumper Cap Error
Indoor Unit
dA
Hardware Address Error
Wired Controller PC-Board
dH
Error
Capacity DIP Switch Setting
dC
Error.
Outlet Air Temperature
dL
Sensor Error
Indoor Unit CO
dE
Error
Special Code:
db
Field Debugging Code
Troubleshooting
Content
Sensor
2