“E9” Water Overflow Protection - Gree U-Match 5 Series Manual

Table of Contents

Advertisement

GREE
3.4.7 "E9" Water Overflow Protection
Error display: IDU wired controller and IDU receiver light board will display E9
Error judgment condition and method:
Check the status of IDU float switch. When water level is too high, float switch is activated, so water full
protection happens.
Possible reason:
■IDU is installed improperly
■Drainage pump is broken
■Float switch operates abnormally
■IDU mainboard is abnormal;
Troubleshooting:
U-Match 5 SERIES UNIT SERVICE MANUAL