Delta Laminator
3.2.6
Error – instrumentation of circuit breaker FA1 for frequency inverter U1
Status indication:
Yellow ERROR indicator is lit up continuously.
Operator's panel, Main Screen, 1st status line:
Operator's panel, Main Screen, 2nd status line:
Error Screen:
Status correction:
Check circuit breaker FA1 in the switchboard.
Turn the circuit breaker to position I.
If the error is still reported on the operator's panel, it is necessary to check the connection of
conductors 217 and 711, which lead to input PLC X37 (See DA-41-100n, sheet 7).
3.2.7
Error - fuse FU12 is broken
Status indication:
Yellow ERROR indicator is lit up continuously.
Operator's panel, Main Screen, 1st status line:
Operator's panel, Main Screen, 2nd status line:
Error Screen:
Status correction:
Check fuse FU12 in the switchboard and if it is broken, replace it.
If the fuse is not broken, check the connection. See DA-41-100n, sheet 2
The electrical potential on conductor No. 218 at input PLC X36 must reach the voltage of 24 Vdc
(See DA-41-100n sheet 7).
3.2.8
Error on IRC of encoder SQ5 or of the main drive
Status indication:
START button/indicator is blinking.
Yellow ERROR indicator is lit up continuously.
Operator's panel, Main Screen, 1st status line:
Operator's panel, Main Screen, 2nd status line:
Error Screen:
© 2004 General Binding Corporation
Circuit breaker
Check circuit breaker
and switch ON
Fuse FU12 is broken
or disconnected wire
Change fuse
or check wiring
Bad IRC encoder
or IRC is disconnected
or motor M1 is not moving
or etc.
Service Manual – Electrical
ERROR
Circuit Breaker
ERROR
Fuse FU12
ERROR
IRC encoder
23