Tracking pump usage
You can find out how much an individual pump has been used by viewing the pump
record parameters.
Information Available
Total running hours for a relay assigned
to a pump.
Other controls
Relays controlled by time
A relay can be controlled by time setpoints using Time of Day or Elapsed Time.
Set Time of Day Relay
Parameter
2. 1 1.2. 1 . Enable
2. 1 1.2.2. Activation Time
2. 1 1.2.3. Relay Duration
2. 1 1.2.4. Assigned Relay
2. 1 1.2.5. Relay Logic
Set Elapsed Time Relay
Parameter
2. 1 1. 1 . 1 . Enable
2. 1 1. 1 .2. Interval
2. 1 1. 1 .3. Relay Duration
2. 1 1. 1 .4. Assigned Relay
2. 1 1. 1 .5. Relay Logic
Page 92
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Parameter Access
3.2.7. 1 . Run Time Relay 2
3.2.7.2. Run Time Relay 3
Value
Enabled
Enables Time of Day Relay
17:30
Activates the relay at 5:30 pm
60
Activates the relay for 60 seconds
Relay 1
Sets relay 1 to be controlled by time of day
Use (if necessary) to change the behaviour of
Normally
the relay assigned to the time of day control.
Closed
Default: Normally Open
Value
Enabled
Enables elapsed time relay
24
Activates the relay every 24 hours
60
Activates the relay for 60 seconds
Relay 1
Sets relay 1 to be controlled by elapsed time
Use (if necessary) to change the behaviour of
Normally
the relay assigned to the elapsed time control.
Closed
Default: Normally Open
Description
Description
A5E33329501