2.8. Alarms
The SITRANS LUT400 supports eight alarm types. Any alarm can be assigned to any
available relay.
It is possible to assign more than one alarm to the same relay. In this case, the relay
will activate if any one of the alarms is activated. If no alarms are activated, the relay
will become inactive.
For details on relay behaviour under fail-safe conditions, see Alarm relays on page
66.
Note: Default settings in the parameter tables are indicated with an asterisk (*)
unless explicitly stated.
2.8.1. High Level Alarm
Reported when material level is within a user-defined range (see 2.8.1.2.High
Level Value ON and 2.8.1.3.High Level Value OFF).
Can be used in conjunction with 2.8.12.Time To Spill feature.
2.8.1.1.
Enables/disables High Level Alarm.
Options
2.8.1.2.
Sets the material level (defined in 2.1.1.Units) at which the High Level Alarm
will activate.
Values
Value must be lower than Level To Spill (2.8.12.1.) if Time to Spill feature is
used.
2.8.1.3.
Sets the material level (defined in 2.1.1.Units) at which the High Level Alarm
will de-activate.
Values
2.8.1.4.
Determines which relay (if any) will be activated when the High Level Alarm
activates.
Options
2.8.1.5.
Read only. Used to view the current state of the High Level Alarm.
Options
Page 162
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Enable
*
High Level Value ON
Range: 0.000 to 99999.000
Default: 0.000
High Level Value OFF
Range: 0.000 to 99999.000
Default: 0.000
Assigned Relay
Alarm State
ENABLED
DISABLED
*
NO RELAY
RELAY 1
RELAY 2
RELAY 3
ACTIVE
INACTIVE
A5E33329501