Palmer Bowlus Flume
Plan View
Side View
* for rated flows under free flow conditions
** The transducer must be above the maximum head by at least the blanking value (see
Near Range
).
Parameter
2.15. 1 . Primary Measuring Device (PMD)
2.15.4. PMD Dimensions
2.15.3.3. Maximum Head
2.15.3.4. Maximum Flow at 20 mA
2.15.3.5. Zero Head Offset
2.15.3.7. Flowrate Units
2.15.3.1. Method of Flow Calculation
Note: Palmer Bowlus Flume can only be setup using ratiometric calculations
Application information
Sized by pipe diameter D
Flume relief is trapezoidal
Designed to install directly into pipelines and manholes
Head is referenced to bottom of the throat, not bottom of the pipe
For rated flows under free flow conditions, the head is measured at a distance of
D/2 upstream from the beginning of the converging section
Page 114
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Flow
D/2, point of measurement*
D = pipe or sewer diameter
Front View
Zero
Head
Value
Palmer Bowlus Flume
Maximum Flume width h
Ratiometric
transducer**
D
2.2.4.
max
A5E33329501