Pump Totalizers

Inflow/Discharge Adjust

Pumped volume totals are affected by the inflow (or discharge) rate. This rate can be
calculated based on rate of change estimation, or pump cycle timing.
Using Inflow/Discharge Adjust (2.7.3.4.), set option Based on rate estimation to have the
inflow rate measured just prior to the start of the pump cycle.
Level
Set option Based on pump cycle to calculate the inflow based on the change of volume
between the end of the last pump cycle and the start of the next one, and the time period
between the last cycle and the current one.
pump down
L
2
Level
L
1
Page 266
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
pump down
well refills
Time
well refills
T
–T
2
1
T
1
Time
L
T
Inflow estimation = L
Inflow estimation = L
L
–L
2
T
2
T
–L
2
1
T
–T
2
1
1
A5E33329501