Siemens SITRANS LUT400 Series Operating Instructions Manual page 369

Hart ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400 Series:
Table of Contents

Advertisement

Available languages

Available languages

ON Setpoint Pump 1
The level at which Pump 1 turns ON, defined in 2.1.1. Units.
Value
ON Setpoint Pump 2
The level at which Pump 2 turns ON, defined in 2.1.1. Units.
Value
OFF Setpoint Pump 1
The level at which Pump 1 turns OFF, defined in 2. 1 . 1 . Units.
Value
OFF Setpoint Pump 2
The level at which Pump 2 turns OFF, defined in 2. 1 . 1 . Units.
Value
End of Wizard - Pump Control
For Wizard to be successful, all changes must be applied.
Options
To transfer values to the device and return to Program menu, press DOWN arrow
(Finish). Then press LEFT arrow
Page 56
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Range: 0.000 to 99999.000
Default: 0.000
Range: 0.000 to 99999.000
Default: 0.000
Range: 0.000 to 99999.000
Default: 0.000
Range: 0.000 to 99999.000
Default: 0.000
BACK, CANCEL, FINISH (Display returns to Pump Control menu when Wizard
is successfully completed or cancelled. If CANCEL is selected, no changes are
written to the device.)
two times to return to Measurement mode.
7ML1998MV01

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Sitrans lut430Sitrans lut440Sitrans lut420

Table of Contents