Siemens SITRANS LUT400 Series Operating Instructions Manual page 519

Hart ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400 Series:
Table of Contents

Advertisement

Available languages

Available languages

3.3.3. Remaining Device Life
Notes:
• Four sets of parameters allow you to monitor the Device/Sensor Lifetimes
and set up Maintenance/Service schedules, based on operating hours
instead of a calendar-based schedule. See also Remaining Sensor Life
(3.3.4.), Service Schedule (3.3.5.), and Calibration Schedule (3.3.6.).
• Performing a reset to Factory Defaults will reset all the Maintenance
Schedule parameters to their factory defaults.
• The device operates in years. To view Remaining Device Lifetime
parameters in hours or days (only via SIMATIC PDM, PACTware FDT, and
AMS) see Lifetime Expected (3.3.3. 1 .).
The device tracks itself based on operating hours and monitors its predicted
lifetime. You can modify the expected device lifetime, set up schedules for
maintenance reminders, and acknowledge them.
The maintenance warnings and reminders are available through HART
communications. This information can be integrated into an Asset
Management system. For optimal use, we recommend that you use SIMATIC
PCS7 Asset Management Software in conjunction with SIMATIC PDM.
To access these parameters via SIMATIC PDM:
Open the menu Device – Maintenance and select the Remaining Device
Lifetime tab. (For more details see
Communications manual.
Time Units
Allows you to set the desired units.
Options
a.
3.3.3.1.
Note: The device always operates in years. Changing the Time Units
affects only the parameter view of the Remaining Device Lifetime
parameters in SIMATIC PDM, PACTware FDT, and AMS.
Allows you to override the factory default.
Values
a.
1.
Communications for SITRANS LUT400 (HART) Manual (7ML19985NE01)
Page 206
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
1
)
HOURS
a
DAYS
* YEARS
Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS.
Lifetime Expected
Units
Range: 0.000 to 20.000 years
Default: 10.000 years
Units are selectable only via SIMATIC PDM, PACTware FDT, and AMS.
Maintenance
in LUT400
a
: hours, days, years
A5E33329501

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Sitrans lut430Sitrans lut440Sitrans lut420

Table of Contents