Siemens SITRANS LUT400 Series Operating Instructions Manual page 482

Hart ultrasonic controllers
Hide thumbs Also See for SITRANS LUT400 Series:
Table of Contents

Advertisement

Available languages

Available languages

2.8.9.5.
Read only. Used to view the current state of the High Flowrate Alarm.
Options
2.8.10. Low Flowrate Alarm
Available only on LUT440 (OCM model).
Reported when the OCM flowrate is within a user-defined range (see
2.8.10.2.Low Flowrate Value ON
2.8.10.1. Enable
Enables/disables Low Flowrate Alarm.
Options
2.8.10.2. Low Flowrate Value ON
Sets the flowrate value (defined in 2.15.3.7.Flowrate Units) at which the Low
Flowrate Alarm will activate.
Values
2.8.10.3. Low Flowrate Value OFF
Sets the material level (defined in 2.15.3.7.Flowrate Units) at which the Low
Flowrate Alarm will de-activate.
Values
2.8.10.4. Assigned Relay
Determines which relay (if any) will be activated when the Low Flowrate
Alarm activates.
Options
2.8.10.5. Alarm State
Read only. Used to view the current state of the Low Flowrate Alarm.
Options
2.8.11. Relay Logic
Relay contact operation is NORMALLY CLOSED for alarms and NORMALLY
OPEN for controls.
By default an alarm contact is Normally Closed. When an alarm activates, the
corresponding relay coil is de-energized. By setting this parameter to Normally
Open, the relay coil will be energized when an alarm assigned to the relay
activates.
A5E33329501
SITRANS LUT400 (HART) – OPERATING INSTRUCTIONS
Alarm State
*
Range: 0 to 9999999
Default: 0
Range: 0 to 9999999
Default: 0
ACTIVE
INACTIVE
2.8.10.3.Low Flowrate Value OFF
and
ENABLED
DISABLED
*
NO RELAY
RELAY 1
RELAY 2
RELAY 3
ACTIVE
INACTIVE
).
Page 169

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Sitrans lut430Sitrans lut440Sitrans lut420

Table of Contents